DYNAMIC ENERGY MODELING OF AN EXPERIMENTAL BUILDING EQUIPPED WITH AN UNDERFLOOR AIR DISTRIBUTION (UFAD) SYSTEM

In this study, experimental and simulation studies were performed in a building equipped with an UFAD system in order to investigate the applicability of a new approach designed for prediction of the energy consumption of a residential building with an UFAD system. In this approach, a zonal model, Pressurized zOnal Model with the Air diffuser (POMA), was coupled with a thermal jet model and integrated into a traditional multizone thermal model. The coupled model was verified experimentally. This integrated model has the ability to take into account the characteristics of an UFAD system and thus accurately simulate its energy consumption. A case study was carried out using both approaches: Multi-zone approach and the new developed integrated zonal/jet/multizone model. A quantitative comparison, in terms of energy demand of a building with an UFAD system, shows that the difference can reach 14% and thus indicates that the traditional multizone modeling approach is not appropriate to use for UFAD system in the building energy prediction.

[1]  Kwang Ho Lee,et al.  Simplified calculation method for design cooling loads in underfloor air distribution (UFAD) systems , 2011 .

[2]  Vice President,et al.  AMERICAN SOCIETY OF HEATING, REFRIGERATION AND AIR CONDITIONING ENGINEERS INC. , 2007 .

[3]  Brent Griffith,et al.  Framework for Coupling Room Air Models to Heat Balance Model Load and Energy Calculations (RP-1222) , 2004 .

[4]  Refrigerating ASHRAE handbook of fundamentals , 1967 .

[5]  P. Heiselberg,et al.  Ventilation of Large Spaces in Buildings: Analysis and Prediction Techniques , 1998 .

[6]  Michael A. Gerber,et al.  EnergyPlus Energy Simulation Software , 2014 .

[7]  Ali F. Alajmi,et al.  Saving energy by using underfloor-air-distribution (UFAD) system in commercial buildings , 2010 .

[8]  Standard Ashrae Thermal Environmental Conditions for Human Occupancy , 1992 .

[9]  F. Haghighat,et al.  Zonal Modeling for Simulating Indoor Environment of Buildings: Review, Recent Developments, and Applications , 2007 .

[10]  Marjorie Musy,et al.  Building Zonal Thermal and Airflow Modelling - A Review , 2005 .

[11]  Kwang Ho Lee,et al.  Influence of raised floor on zone design cooling load in commercial buildings , 2010 .

[12]  Fariborz Haghighat,et al.  Development and validation of a zonal model — POMA , 2001 .

[13]  Qingyan Chen,et al.  On approaches to couple energy simulation and computational fluid dynamics programs , 2002 .

[14]  Tom Webster,et al.  Heat transfer pathways in underfloor air distribution (UFAD) systems , 2006 .