A Study of Non-Detection Zone using AFD Method applied to Grid-Connected Photovoltaic Inverter for a variety of Loads
暂无分享,去创建一个
Islanding phenomenon of utility-connected photovoltaic power conditioning systems(PV PCS) can cause a variety of problems and must be prevented. If the real and reactive power supplied by PV PCS are closely matched to those of load, islanding detection by passive methods becomes difficult. The active frequency drift(AFD) method, called the frequency bias method, enables islanding detection by forcing the frequency of the voltage in the islanding to drift up or down. In this paper, non-detection zone(NDZ) of AFD is analyzed for the islanding detection method of utility-connected PV PCS by the simulation software tool PSIM.