Novel control techniques of Petersen-coil

Most Chinese medium voltage (MV) power systems have been operated with neutral resonance grounded. The resonance grounding method is hard to completely satisfy the requirement of suppressing normal neutral-to-ground voltage and self-extinguishing arc grounding faults in distribution network with high asymmetry, where Peterson-coil automatic tuning is also difficult to be implemented. In order to improve them, some novel control techniques of Petersen-coil are proposed in the paper. They include a new grounding method based on Petersen-coil in parallel with a reactor, a novel method for measuring insulation parameters to ground, and a novel control strategy of Petersen-coil. Dynamic power system experimentations are carried out. Experimentation results show that the proposed neutral grounding method can restrain normal voltage of neutral point and ensure arc grounding fault self-extinguished, the proposed measurement method of insulation parameters is simple, convenient, precise and tested in real time without power supply interrupting.

[1]  Xianggen Yin,et al.  A novel technique for measuring grounding capacitance and grounding fault resistance in ineffectively grounded systems , 2000 .

[2]  J. Sottile,et al.  An overview of fault monitoring and diagnosis in mining equipment , 1994 .

[3]  T. Novak,et al.  Technological innovations in deep coal mine power systems , 1995, IAS '95. Conference Record of the 1995 IEEE Industry Applications Conference Thirtieth IAS Annual Meeting.

[4]  Jiang Xin-yu Research on capacitive current measurement with signal injection in distribution network , 2004 .

[5]  Zeng Xiangjun,et al.  Grounding faulted feeder detection with fault resistance measurement in mining power systems , 2005, Fourtieth IAS Annual Meeting. Conference Record of the 2005 Industry Applications Conference, 2005..

[6]  Raoul Willheim,et al.  Neutral Grounding in High-Voltage Transmission , 1956 .

[7]  Liu Li A NEW METHOD TO MEASURE CAPACITANCE CURRENT IN DISTRIBUTION NETWORK , 2001 .

[8]  Yin Xianggen,et al.  On-site safety evaluation for earth fault in mining power systems , 2001, Conference Record of the 2001 IEEE Industry Applications Conference. 36th IAS Annual Meeting (Cat. No.01CH37248).