Winding movement and condition monitoring of power transformers in service

Power transformers are the most expensive pieces of equipment in a power substation. It is very important to prevent failures and detect problems in a transformer as early as possible. This thesis reviews the diagnostic and monitoring tests and equipment available to assess the condition of transformers and to provide an early warning of potential failure. One problem that is particularly difficult to detect is winding looseness, which can cause movement of the windings and may cause transformer failure. If the looseness or movement can be detected over time, action can be taken to prevent such failures. Frequency Response Analysis (FRA) techniques have the potential to detect winding problems, but the method also contains some uncertainty. In this thesis, Experiments on off-line and online FRA techniques were performed both in the laboratory and on transformers in the field throughout North America. New data assessment methods were developed that will help interpret future on-site transformer condition assessment tests. The key test circuit parameters and their effects on frequency response measurements were studied, covering issues such as the effects that external measurement leads and high voltage bushings on the test results, measuring shunt impedance, requirements for recording equipment, the measurement frequency ranges to identify winding problems, the measurement frequency range related to the amount of winding movement, criteria to be used for winding movement ranking, etc. A computer simulation was conducted on a simplified network transformer model. The principal findings from the simulation are similar to the experimental work. Based on the experimental investigation of the FRA method and the transformer model simulation, a new FRA technique was developed that is feasible for on-line applications or for monitoring on-site. To overcome the shortcomings of the existing FRA method, such as frequency limitations and on-line application, the High-Frequency Internal Frequency Response Analysis method (HIFRA) was developed. It uses an injected wide-band frequency signal through the transformer bushing, in combination with an internal FRA measurement. This new technique is very promising for future application for on-line FRA measurements. TABLE OF CONTENTS ABSTRACT ii TABLE OF CONTENTS . < iii LIST OF TABLES v LIST OF FIGURES vi GLOSSARY OF ABBREVIATIONS xi ACKNOWLEDGEMENT xii CHAPTER I OVERVIEW 1 1.

[1]  V. Woivre,et al.  Transient overvoltage study and model for shell-type power transformers , 1993 .

[2]  Tapan Kumar Saha,et al.  Investigations into effective methods for assessing the condition of insulation in aged power transformers , 1998 .

[3]  C. Bengtsson,et al.  Status and trends in transformer monitoring , 1996 .

[4]  Tapan Kumar Saha,et al.  Electrical and chemical diagnostics of transformers insulation. B. Accelerated aged insulation samples , 1997 .

[5]  Y. Shibuya,et al.  Analysis of very fast transient overvoltage in transformer winding , 1997 .

[6]  A. S. Morched,et al.  A high frequency transformer model for the EMTP , 1993 .

[7]  E.P. Dick,et al.  Transformer Diagnostic Testing by Frequuency Response Analysis , 1978, IEEE Transactions on Power Apparatus and Systems.

[8]  M. K. Domun Condition monitoring of power transformers , 1990 .

[9]  L. Haydock,et al.  Swept frequency response test for condition monitoring of power transformer , 1995, Proceedings:Electrical Electronics Insulation Conference and Electrical Manufacturing & Coil Winding Conference.

[10]  R. C. Degeneff,et al.  A method for constructing a reduced order transformer model for system studies from detailed lumped parameter models , 1991 .

[11]  T Adielson,et al.  Resonant Overvoltages in EHV Transformers-Modeling and Application , 1981, IEEE Transactions on Power Apparatus and Systems.

[12]  D. Yannucci,et al.  "On-Line Monitoring of Power Transformers" , 1985, IEEE Transactions on Power Apparatus and Systems.

[13]  Ryszard Malewski,et al.  Measurement of switching transients in 735 kV substations and assessment of their severity for transformer insulation , 1988 .

[14]  T. Leibfried,et al.  Online monitors keep transformers in service , 1998 .

[15]  W. Walter,et al.  On-line diagnostics of high-voltage bushings and current transformers using the sum current method , 2000 .

[16]  Ryszard Malewski,et al.  Impulse testing of power transformers using the transfer function method , 1988 .

[17]  Hossein Borsi,et al.  A continuous parameter high frequency model based on travelling waves for transformer diagnostic purposes , 2002, Conference Record of the the 2002 IEEE International Symposium on Electrical Insulation (Cat. No.02CH37316).

[18]  Hossein Borsi,et al.  Diagnostic methods for transformers on-site , 1998, Proceedings of 1998 International Symposium on Electrical Insulating Materials. 1998 Asian International Conference on Dielectrics and Electrical Insulation. 30th Symposium on Electrical Insulating Ma.

[19]  A. E. Davies,et al.  PD pattern identification using acoustic emission measurement and neural networks , 1999 .

[20]  George C. Verghese,et al.  Parametric System Identification on Logarithmic Frequency Response Data , 1990, 1990 American Control Conference.

[21]  A.J. McElroy On the significance of recent EHV transformer failures involving winding resonance , 1975, IEEE Transactions on Power Apparatus and Systems.

[22]  J. Schoukens,et al.  Parametric identification of transfer functions in the frequency domain-a survey , 1994, IEEE Trans. Autom. Control..

[23]  T. C. Cheng,et al.  Analysis and suppression of continuous periodic interference for on-line PD monitoring of power transformers , 1999 .

[24]  W. R. Rutgers,et al.  On-line partial discharge monitoring of HV components , 1999 .

[25]  J. M. Schneider,et al.  Rockport Transient Voltage Monitoring System: Analysis and Simulation of Recorded Waveforms , 1989, IEEE Power Engineering Review.

[26]  Yilu Liu,et al.  Transient response prediction of power system equipment using a frequency domain impedance function model , 1995 .

[27]  Y. Liu,et al.  Modeling of converter transformers using frequency domain terminal impedance measurements , 1993 .

[28]  Jose R. Marti,et al.  Simplified three-phase transformer model for electromagnetic transient studies , 1995 .

[29]  Ali Abur,et al.  Identification of high frequency transformer model parameters , 1997 .

[30]  E. Nemeth,et al.  Measuring voltage response: a non-destructive diagnostic test method of HV insulation , 1999 .

[31]  G. Csepes,et al.  Practical foundations of the RVM (recovery voltage method for oil/paper insulation diagnosis) , 1998, 1998 Annual Report Conference on Electrical Insulation and Dielectric Phenomena (Cat. No.98CH36257).

[32]  H. P. Chou,et al.  Monitoring the health of power transformers , 1996 .

[33]  W. S. Zaengl,et al.  Development and application of new condition assessment methods for power transformers , 1998 .

[34]  A. Keyhani,et al.  Parameter Estimation for Power Transformer Models from Time-Domain Data , 1986, IEEE Transactions on Power Delivery.

[35]  R. Rogers IEEE and IEC Codes to Interpret Incipient Faults in Transformers, Using Gas in Oil Analysis , 1978, IEEE Transactions on Electrical Insulation.

[36]  Yan Zhang,et al.  Study on trend analysis method for on-line insulation diagnosing of capacitive-type equipment , 1998, Proceedings of 1998 International Symposium on Electrical Insulating Materials. 1998 Asian International Conference on Dielectrics and Electrical Insulation. 30th Symposium on Electrical Insulating Ma.

[37]  Gevork B. Gharehpetian,et al.  Hybrid modelling of inhomogeneous transformer winding for very fast transient overvoltage studies , 1998 .

[38]  P. M. Eleftherion Partial discharge. XXI. Acoustic emission based PD source location in transformers , 1995 .

[39]  J. P. Reynders,et al.  Winding slackness monitoring as a diagnostic for insulation ageing in oil-paper insulated power transformers , 1999 .

[40]  J. P. Reynders,et al.  Failures in power system transformers and appropriate monitoring techniques , 1999 .

[41]  Tapan Kumar Saha,et al.  Electrical and chemical diagnostics of transformers insulation. A. Aged transformer samples , 1997 .

[42]  P. J. Griffin,et al.  Neural net and expert system diagnose transformer faults , 2000 .

[43]  Chen Weigen,et al.  On-line detection of gases dissolved in transformer oil and the faults diagnosis , 1998, Proceedings of 1998 International Symposium on Electrical Insulating Materials. 1998 Asian International Conference on Dielectrics and Electrical Insulation. 30th Symposium on Electrical Insulating Ma.

[44]  Thomas Henry Crowley Automated diagnosis of large power transformers using adaptive model-based monitoring , 1990 .

[45]  M. Waters,et al.  The short-circuit strength of power transformers , 1966 .

[46]  Gerard Ledwich,et al.  Identification of high frequency transformer equivalent circuit using Matlab from frequency domain data , 1997, IAS '97. Conference Record of the 1997 IEEE Industry Applications Conference Thirty-Second IAS Annual Meeting.

[47]  D. Wenzel,et al.  Analytical computation of the transfer functions of transformers , 1998, Proceedings of 1998 International Symposium on Electrical Insulating Materials. 1998 Asian International Conference on Dielectrics and Electrical Insulation. 30th Symposium on Electrical Insulating Ma.

[48]  L. Satish,et al.  Short-time Fourier and wavelet transforms for fault detection in power transformers during impulse tests , 1998 .

[49]  Brett Ninness,et al.  Subspace-based identification of power transformer models from frequency response data , 1999, IEEE Trans. Instrum. Meas..

[50]  M. Duval,et al.  Dissolved gas analysis: It can save your transformer , 1989, IEEE Electrical Insulation Magazine.

[51]  R. Sahu Optimization of the transmission and subtransmission transformer spares on the AEP system , 1980 .

[52]  S. Tenbohlen,et al.  Enhanced Diagnosis of Power Transformers using On-and Off-line Methods : Results , Examples and Future Trends , .

[53]  T. Leibfried Online monitoring of power transformers-system technology and data evaluation , 1999 .

[54]  Y. Liu,et al.  Power transformer resonance-measurements and prediction , 1992 .

[55]  B. Sparling Transformer monitoring and diagnostics , 1999, IEEE Power Engineering Society. 1999 Winter Meeting (Cat. No.99CH36233).

[56]  K. D. Srivastava,et al.  Condition monitoring of transformers in service by the low voltage impulse test method , 1999 .

[57]  Robert N. Jacques,et al.  Identification of highly accurate low order state space models in the frequency domain , 1996, Signal Process..

[58]  J. A. Lapworth,et al.  Condition assessment techniques for large power transformers , 1995 .

[59]  Robert N. Jacques,et al.  Frequency domain structural system identification by observability range space extraction , 1994, Proceedings of 1994 American Control Conference - ACC '94.

[60]  A. J. Marques Cardoso,et al.  Condition monitoring and diagnostics of power transformers , 1998 .

[61]  L. Ljung,et al.  Subspace-based multivariable system identification from frequency response data , 1996, IEEE Trans. Autom. Control..

[62]  P.T.M. Vaessen Transformer model for high frequencies , 1988 .

[63]  L. Satish,et al.  Multiresolution signal decomposition: a new tool for fault detection in power transformers during impulse tests , 1998 .

[64]  A. O. Soysal A method for wide frequency range modeling of power transformers and rotating machines , 1991 .

[65]  A. Zargari,et al.  Application of optical fibre sensor for partial discharge detection in high-voltage power equipment , 1996, Proceedings of Conference on Electrical Insulation and Dielectric Phenomena - CEIDP '96.

[66]  Ieee Standards Board IEEE guide for the interpretation of gases generated in oil-immersed transformers , 1992 .

[67]  C. K. Mechefske Correlation power transformer tank vibration characteristics to winding looseness , 1995 .

[68]  P. Purkait,et al.  Pattern classification of impulse faults in transformers by wavelet analysis , 2002 .

[69]  V. Brandwajn,et al.  Matrix Representation of Three-Phase N-Winding Transformers for Steady-State and Transient Studies , 1982, IEEE Transactions on Power Apparatus and Systems.

[70]  Ajit S. Bopardikar,et al.  Wavelet transforms - introduction to theory and applications , 1998 .

[71]  Transformer monitoring using the UHF technique , 1999 .

[72]  Yasuo Okazaki,et al.  Vibration Analysis of a 3- Phase Model Transformer Core , 1996 .

[73]  T. Leibfried,et al.  Monitoring of power transformers using the transfer function method , 1999 .

[74]  G. M. Urbani,et al.  Using the recovery voltage method to evaluate aging in oil-paper insulation , 1998, ICSD'98. Proceedings of the 1998 IEEE 6th International Conference on Conduction and Breakdown in Solid Dielectrics (Cat. No.98CH36132).

[75]  J. Bak-Jenson,et al.  Parametric identification in potential transformer modelling , 1992 .

[76]  S. R. Kannan,et al.  Generator loading limits for impulse testing low-inductance windings , 1975 .

[77]  Mats Leijon,et al.  A major Breakthrough in Transformer Technology , 2000 .

[78]  F. de Leon,et al.  Reduced order model for transformer transients , 1992 .

[79]  S. Birlasekaran,et al.  Off/on-line FRA condition monitoring technique for power transformer , 1999 .

[80]  A. Garcia-Cerrada,et al.  Experiences learned from the on-line internal monitoring of the behaviour of a transformer , 1997, 1997 IEEE International Electric Machines and Drives Conference Record.

[81]  J. B. DiGiorgio,et al.  Cut failures by analyzing transformer oil , 1979 .

[82]  V. I. Kogan,et al.  Failure analysis of EHV transformers , 1988 .

[83]  B. T. Phung,et al.  On-line partial discharge measurement on instrument transformers , 1998, Proceedings of 1998 International Symposium on Electrical Insulating Materials. 1998 Asian International Conference on Dielectrics and Electrical Insulation. 30th Symposium on Electrical Insulating Ma.