Indoor pollutant mixing time in an isothermal closed room: An investigation using CFD

We report on computational fluid dynamics (CFD) predictions of mixing time of a pollutant in an unventilated, mechanically mixed, isothermal room. The study aims to determine: (1) the adequacy of the standard Reynolds Averaged Navier Stokes two-equation ({kappa}-{var_epsilon}) turbulence model for predicting the mixing time under these conditions and (2) the extent to which the mixing time depends on the room airflow, rather than the source location within the room. The CFD simulations modeled the 12 mixing time experiments performed by Drescher et al. (Indoor Air 5 (1995) 204) using a point pulse release in an isothermal, sealed room mechanically mixed with variable power blowers. Predictions of mixing time were found in good agreement with experimental measurements, over an order of magnitude variation in blower power. Additional CFD simulations were performed to investigate the relation between pollutant mixing time and source location. Seventeen source locations and five blower configurations were investigated. Results clearly show large dependence of the mixing time on the room airflow, with some dependence on source location. We further explore dependence of mixing time on the velocity and turbulence intensity at the source location. Implications for positioning air-toxic sensors in rooms are briefly discussed.

[1]  U. Hoegg Cigarette smoke in closed spaces. , 1972, Environmental health perspectives.

[2]  A. Gadgil,et al.  Mixing of a point-source indoor pollutant: Numerical predictions and comparison with experiments , 2002 .

[3]  Ashok J. Gadgil,et al.  Mixing of a Point‐Source Indoor Pollutant by Forced Convection , 1995 .

[4]  J. Samet,et al.  Environmental tobacco smoke concentrations in no-smoking and smoking sections of restaurants. , 1993, American journal of public health.

[5]  Halûk Özkaynak,et al.  Indoor air quality modeling: Compartmental approach with reactive chemistry , 1982 .

[6]  William W. Nazaroff,et al.  Mixing of a Point Source Pollutant by Natural Convection Flow within a Room , 1994 .

[7]  J. Behar,et al.  Modeling indoor air concentrations near emission sources in imperfectly mixed rooms. , 1996, Journal of the Air & Waste Management Association.

[8]  S. Patankar Numerical Heat Transfer and Fluid Flow , 2018, Lecture Notes in Mechanical Engineering.

[9]  M. J. Craig,et al.  Pollutant transport and dispersion in large indoor spaces: A status report for the large space effort of the Interiors Project , 2000 .

[10]  Steven E. Benzley,et al.  Civil and Environmental Engineering , 2004 .

[11]  Yoshiaka. Ishizu,et al.  General equation for the estimation of indoor pollution. , 1980 .

[12]  A. Gadgil,et al.  Computed tomography and optical remote sensing: development for the study of indoor air pollutant transport and dispersion , 1995 .

[13]  Per Heiselberg,et al.  Room Air and Contaminant Distribution in Mixing Ventilation , 1996 .

[14]  J. Behar,et al.  Modeling Indoor Air Concentrations Near Emission Sources in Imperfectly Mixed Rooms. , 1996, Journal of the Air & Waste Management Association.