The process of self excitation in induction generators

The phenomenon of self excitation in induction machines is examined and a physical interpretation of how self excitation occurs is presented. The important parameters are shown to be the shaft speed, the residual magnetism, the reduced permeability at low magnetisation, and the size of the capacitor connected to the machine. The results are important in applications where induction machines are used as stand-alone generators for a power system, as the reliability of self excitation in such cases must be very high.

[1]  F. De Mello,et al.  Large Scale Induction Generators for Power Systems , 1981, IEEE Transactions on Power Apparatus and Systems.

[2]  R. G. Harley,et al.  Subsynchronous resonance of single-cage induction motors , 1981 .

[3]  C. F. Wagner,et al.  Self-excitation of induction motors , 1939, Electrical Engineering.

[4]  B. R. Teare Theory of hysteresis-motor torque , 1940, Electrical Engineering.

[5]  I. R. Smith,et al.  Transients in induction machines with terminal capacitors , 1968 .

[6]  O. E. Mainer Theoretical Treatment of Permanent Magnet Alternators , 1968 .

[7]  C. F. Wagner,et al.  Self-excitation of induction motors with series capacitors , 1941, Electrical Engineering.

[8]  J. E. Barkle,et al.  Induction Generator Theory and Application [includes discussion] , 1954, Transactions of the American Institute of Electrical Engineers Part III Power Apparatus and Systems.