Measurement and analysis of electromagnetic disturbances in 500kV DC converter station
暂无分享,去创建一个
This paper analyzes the major electromagnetic disturbance sources and their characteristics in high voltage converter station, and measures the electromagnetic disturbance in Heihe 500kV DC converter station. The measurement results shows that opening and closing process of converter valve will produce a continuous broadband electromagnetic disturbance which is much more serious in the range of MHz and declines with frequency rising. The electromagnetic disturbances above 20MHz are all fixed frequencies. And electromagnetic disturbances of high frequency are mainly for mobile phone communication signals and WIFI signals.
[1] S. E. Wright,et al. HDVC converter station tests in the 0.1 to 5 MHz frequency , 1988 .
[2] Wang Qi. Analysis of Electromagnetic Disturbance from Valve Hall in Convert Station , 2010 .
[3] Wu Gui-fang. ELECTROMAGNETIC ENVIRONMENT PROBLEM BROUGHT ABOUT BY ±500kV DC TRANSMISSION PROJECT IN CHINA , 2005 .