지열원 시스템 히트펌프의 냉방 성능 특성에 관한 실증 연구
暂无分享,去创建一个
Recently, small and medium-sized buildings have employed a multi-heat pump. The major benefits of the mulit-heat pump over a conventional system are that it is easier system to maintain along with a diversification of facility use, and high comfortability. The performance of multi-heat pump systems can be enhanced by using geothermal energy instead of air source energy. This paper describes the multi-heat pumps applied in an ground source heat pump system for an actual building. The performance of a ground source multi-heat pump installed in the field was investigated in cooling mode. The maximum COP of the systems with single U-tube and double tube ground loop heat exchangers were 6.6 and 6.0, respectively. It is suggested that the new algorithms to control the flow rate of secondary fluid for ground loop heat exchanger have to be developed in order to enhance the performance of the system.