The following AC electrical power sources shall be OPERABLE: a. Two qualified circuits between the offsite transmission network and the onsite Class 1E AC Electrical Power Distribution System; and b. Two diesel generators (DGs) each capable of supplying one train of the onsite Class 1E AC Electrical Power Distribution System. ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One required offsite circuit A.1 Perform SR 3.8.1.1 for 1 hour inoperable. OPERABLE required offsite circuit. AND Once per 12 hours thereafter AND A.2 Declare required feature(s) 24 hours from with no offsite power discovery of no available inoperable when offsite power to one its redundant required train concurrent with feature(s) is inoperable. inoperability of redundant required feature(s)