Accurate Measurement of Fault Currents Contaminated With Decaying DC Offset and CT Saturation

Decaying dc offset and current-transformer (CT) saturation are the main obstacles to accurate measurement of the fundamental frequency component of fault currents. So far, most of the research works have focused exclusively on only one of these obstacles. However, very recently, research has been directed toward new current measurement algorithms which can deal with both of these issues simultaneously. Using least error squares technique and a simple offline lookup table, this paper introduces a novel method to filter out the decaying dc component and the effects of CT saturation. The proposed algorithm provides the fundamental sinusoidal component of current accurately. This method can respond using only five current samples. Meanwhile, the window size could also be increased to provide more immunity against noise and harmonics. High speed and accuracy, together with the simplicity and noise immunity of the proposed method, can make it a practical solution to address the decaying dc offset and CT saturation problems. Numerous simulated and real fault currents as well as real-time hardware implementation verify the effectiveness of the proposed algorithm.

[1]  L. Schiel,et al.  Correction of Current Transformer Transient Performance , 2008, IEEE Transactions on Power Delivery.

[2]  Soon-Ryul Nam,et al.  An Analytic Method for Measuring Accurate Fundamental Frequency Components , 2002 .

[3]  Jyh-Cherng Gu,et al.  Removal of decaying DC in current and voltage signals using a modified Fourier filter algorithm , 2001 .

[4]  Khoi Vu,et al.  An efficient compensation algorithm for current transformer saturation effects , 2004, IEEE Transactions on Power Delivery.

[5]  Gerhard Ziegler,et al.  Numerical Differential Protection: Principles and Applications , 2005 .

[6]  K. Erenturk,et al.  ANFIS-Based Compensation Algorithm for Current-Transformer Saturation Effects , 2009, IEEE Transactions on Power Delivery.

[7]  H. Khorashadi-Zadeh,et al.  Correction of saturated current transformers secondary current using ANNs , 2006, IEEE Transactions on Power Delivery.

[8]  David C. Lay,et al.  Linear Algebra and Its Applications, 4th Edition , 1994 .

[9]  M. Davarpanah,et al.  Fast and Reliable CT Saturation Detection Using a Combined Method , 2009, IEEE Transactions on Power Delivery.

[10]  Mladen Kezunovic,et al.  Splified Algorithms for Removal of the Effect of Exponentially Decaying DC Offset on the Fourirer Algorithm , 2002, IEEE Power Engineering Review.

[11]  Hong-Jun Yoon,et al.  Correction of current transformer distorted secondary currents due to saturation using artificial neural networks , 2001 .

[12]  Tarlochan S. Sidhu,et al.  Discrete-Fourier-transform-based technique for removal of decaying DC offset from phasor estimates , 2003 .

[13]  J.-A. Jiang,et al.  Application of combined adaptive Fourier filtering technique and fault detector to fast distance protection , 2006, IEEE Transactions on Power Delivery.

[14]  Ying-Yi Hong,et al.  Compensation of Distorted Secondary Current Caused by Saturation and Remanence in a Current Transformer , 2010, IEEE Transactions on Power Delivery.

[15]  G. Benmouyal,et al.  Removal of DC-offset in current waveforms using digital mimic filtering , 1995 .

[16]  Peter Crossley,et al.  Compensation of the distortion in the secondary current caused by saturation and remanence in a CT , 2004 .

[17]  T. Sidhu,et al.  A new half-cycle phasor estimation algorithm , 2005, IEEE Transactions on Power Delivery.

[18]  Gilsoo Jang,et al.  An Innovative Decaying DC Component Estimation Algorithm for Digital Relaying , 2009, IEEE Transactions on Power Delivery.

[19]  Y. Kang,et al.  Fourier Transform-Based Modified Phasor Estimation Method Immune to the Effect of the DC Offsets , 2009, IEEE Transactions on Power Delivery.

[20]  Soon-Ryul Nam,et al.  Phasor Estimation in the Presence of DC Offset and CT Saturation , 2009, IEEE Transactions on Power Delivery.

[21]  M.S. Sachdev,et al.  A New Algorithm for Digital Impedance Relays , 1979, IEEE Transactions on Power Apparatus and Systems.

[22]  Chi-Shan Yu,et al.  Detection and Correction of Saturated Current Transformer Measurements Using Decaying DC Components , 2010, IEEE Transactions on Power Delivery.

[23]  Udaya Annakkage,et al.  A current transformer model based on the Jiles-Atherton theory of ferromagnetic hysteresis , 2000 .

[24]  Seong Ho Kang,et al.  Busbar differential protection in conjunction with a current transformer compensating algorithm , 2008 .

[25]  Furong Li,et al.  Combined wavelet transform and regression technique for secondary current compensation of current transformers , 2002 .

[26]  C. Muscas,et al.  A digital compensation method for improving current transformer accuracy , 2000 .

[27]  C. Yu A discrete Fourier transform-based adaptive mimic phasor estimator for distance relaying applications , 2006, IEEE Transactions on Power Delivery.