항온시설물에 대한 현열 및 잠열 에너지 회수시스템의 성능해석

A sizing of sensible and latent energy recovery system with condensing heat exchanger is important to the design of a thermally controlled facilities. The transient system simulation program TRNSYS 14.2/IISiBat has been used to evaluate the energy consumptions of a thermally controlled facilities which consist of boiler, chiller and condensing heat exchanger. The boiler and chiller are selected based on the annual peak loads and controlled to maintain the setting temperature of 14~17℃. Simulation shows that the amount of sensible and latent energy recovered by heat exchanger is almost 20% of total heating load.