Contaminant Intrusion through Leaks in Water Distribution System: Experimental Analysis☆

Abstract This paper presents the results of experimental tests on the intrusion of contaminant through pipe cracks in water distribution network resulting from low/negative pressures. The tests were carried out on a looped distribution network at the University of Enna and were performed first producing a pressure transient that causes negative pressures then reproducing intermittent supply. A soluble contaminant was added to the water volume in the network through a pipe crack. Sampling of water volume was carried out in two nodes of the network and the contaminant concentrations were measured. It was showed that: the contaminant was drawn in and transported, in the first set of tests; the contaminant was carried through the network to the point-of-use when the pipes become completely full and the distribution system was in steady state conditions, in the second, and that the concentrations was higher than in the first set of tests.

[1]  Mark W. LeChevallier,et al.  Occurrence of Transient Low and Negative Pressures in Distribution Systems , 2004 .

[2]  F. Cubillo Impact of end uses knowledge in demand strategic planning for Madrid , 2005 .

[3]  Joby Boxall,et al.  Influence of Ground Conditions on Intrusion Flows through Apertures in Distribution Pipes , 2013 .

[4]  F. Cubillo Droughts, risk management and reliability , 2004 .

[5]  Michèle Prévost,et al.  Low and Negative Pressures in Distribution Systems: Do They Actually Result in Intrusion? , 2007 .

[6]  Thomas M. Walski,et al.  Hydraulic transients cause low‐pressure problems , 1994 .

[7]  Mark W. LeChevallier,et al.  Potential for pathogen intrusion during pressure transients , 2003 .

[8]  S. James,et al.  Controlling water quality in intermittent supply systems , 2003 .

[9]  G. La Loggia,et al.  Analysis of the impact of intermittent distribution by modelling the network-filling process , 2011 .

[10]  Bryan W. Karney,et al.  Intrusion Modelling and the Effect of Ground Water Conditions , 2011 .

[11]  Melinda Friedman,et al.  The potential for health risks from intrusion of contaminants into the distribution system from pressure transients. , 2003, Journal of water and health.

[12]  Steven G. Buchberger,et al.  Assessing Intrusion Susceptibility in Distribution Systems , 2002 .

[13]  C. M. Fontanazza,et al.  A model of the filling process of an intermittent distribution network , 2010 .

[14]  Gregory J. Kirmeyer,et al.  PRACTICAL GUIDELINES FOR Maintaining distribution system WATER QUALITY , 2001 .