Groundwater Heat Pump (GWHP) system modeling and Thermal Affected Zone (TAZ) prediction reliability: Influence of temporal variations in flow discharge and injection temperature

Abstract A fundamental aspect in Groundwater Heat Pump (GWHP) plant design is the correct evaluation of the Thermal Affected Zone (TAZ) that develops around the injection well, which is important to avoid interference with existing groundwater applications and underground infrastructure. Numerical methods facilitate the identification of temperature anomalies, and software tools such as the FEFLOW program used in this study assist in these determinations. The actual flow rate and injection temperature are highly time-variable and follow changes in building energy requirements. In order to accurately predict the TAZ, it is necessary to consider this time variability. We calculated the TAZ using hourly discharge flow and temperature data, then recalculated the TAZ using average daily, monthly, and seasonal energetic equivalents. The four simulation results were compared with groundwater temperature data measured using a downgradient piezometer in order to assess the reliability of the simulations. The quality of the simulation was satisfactory when hourly, daily, or monthly flow rate and injection temperature data were used, whereas the seasonal averages were not suitable for reliably assessing TAZ development.

[1]  Giorgia Baccino,et al.  Different design scenarios related to an open loop groundwater heat pump in a large building: Impact , 2011 .

[2]  Zhifang Zhou,et al.  Simulation of Thermal Transport in Aquifer: A GWHP System in Chengdu, China , 2009 .

[3]  Junjun Liang,et al.  Numerical Model for the Capacity Evaluation of Shallow Groundwater Heat Pumps in Beijing Plain, China , 2011 .

[4]  John W. Lund,et al.  Direct utilization of geothermal energy 2010 worldwide review , 2011 .

[5]  Eunjoo Lee,et al.  The investigation of one step annealing for plated Ni/Cu contact solar cells , 2012 .

[6]  Vicky L. Freedman,et al.  Assessing the thermal environmental impacts of an groundwater heat pump in southeastern Washington State , 2012 .

[7]  Georgios A. Florides,et al.  Ground heat exchangers—A review of systems, models and applications , 2007 .

[8]  Jong Min Choi,et al.  Design and performance study of the ground-coupled heat pump system with an operating parameter , 2012 .

[9]  V. A. Fry,et al.  Lessons from London: regulation of open-loop ground source heat pumps in central London , 2009 .

[10]  Stefano Lo Russo,et al.  Hydrogeological and thermal characterization of shallow aquifers in the plain sector of Piemonte region (NW Italy): implications for groundwater heat pumps diffusion , 2010 .

[11]  R. Ooka,et al.  Numerical simulation of ground heat and water transfer for groundwater heat pump system based on real-scale experiment , 2010 .

[12]  David Banks,et al.  Thermogeological assessment of open-loop well-doublet schemes: a review and synthesis of analytical approaches , 2009 .

[13]  Massimo Civita,et al.  Open-loop groundwater heat pumps development for large buildings: A case study , 2009 .

[15]  Petar Vasiljević,et al.  Criteria for use of groundwater as renewable energy source in geothermal heat pump systems for building heating/cooling purposes , 2010 .

[16]  Jozsef Hecht-Méndez,et al.  Evaluating MT3DMS for Heat Transport Simulation of Closed Geothermal Systems , 2010, Ground water.

[17]  Vittorio Verda,et al.  Development of the thermally affected zone (TAZ) around a groundwater heat pump (GWHP) system: A sensitivity analysis , 2012 .

[18]  Marc A. Rosen,et al.  Geothermal heat pump systems: Status review and comparison with other heating options , 2013 .

[19]  Giorgia Baccino,et al.  Energy and environmental analysis of an open-loop ground-water heat pump system in an urban area , 2010 .