Performance evaluation of a stratified chilled-water thermal storage system
暂无分享,去创建一个
In countries with hot climates, air-conditioning forms a large proportion of annual peak electrical demand, requiring expansion of power plants to meet the peak demand, which goes unused most of the time. Use of well-designed cool storage can offset the peak demand to a large extent. In this study, an air conditioning system with naturally stratified storage tank was designed, constructed and tested. A new type of diffuser was designed and used in this study. Factors that influence the performance of chilled water storage tanks were investigated. The results indicated that stratified storage tank consistently stratified well without any physical barrier. Investigation also showed that storage efficiency decreased with increasing flow rate due to increased mixing of warm and chilled water. Diffuser design and layout primarily affected the mixing near the inlet diffuser and the extent of this mixing had primary influence on the shape of the thermocline. The heat conduction through tank walls and through the thermocline caused widening of mixed volume. Thermal efficiency of stratified storage tanks was as high as 90 percent, which indicates that stratified tanks can effectively be used as a load management technique. Keywords—Cool Thermal Storage, Diffuser, Natural Stratification, Efficiency Improvement, Load management.
[1] M. W. Wilden,et al. Evaluation of stratified chilled-water storage techniques. Volume 2. Appendixes. Final report , 1985 .
[2] H. E. Hudson,et al. Dividing-Flow Manifolds with Square-Edged Laterals , 1979 .
[3] R L Cole,et al. THERMALLY STRATIFIED TANKS , 1982 .
[4] C. R. Truman,et al. Initial formation of a thermocline in stratified thermal storage tanks , 1986 .