A prediction of distribution transformers aging based on tank infrared temperature measurements

This paper aims to establish criteria that correlate the distribution transformer tank temperature with the top-oil temperature, a parameter used to compute the life expectance. Therefore, an easy reading on the tank thermal behaviour through an infrared camera could be converted in a top-oil temperature. The results by the proposed methodology shown errors lower than 4°C. Consequently, this technique appears to offer an opportunity to improve the evaluation criteria for overload distribution transformer and the management of equipment overload capability. (4 pages)

[1]  R. Siregar,et al.  Evaluation condition of transformer based on infrared thermography results , 2009, 2009 IEEE 9th International Conference on the Properties and Applications of Dielectric Materials.

[2]  Michael Alan Kregg Benefits of using infrared thermography in utility substations , 2004, SPIE Defense + Commercial Sensing.