Effect of earth current return model on transmission line fault location - a case study

Impedance-based fault location algorithms require positive- and zero-sequence line impedance to determine the distance to fault. When solving for these line constants in a multi-grounded transmission system, power system analysis programs use Carson's model, modified Carson's model or Deri model to account for earth current return. The study is motivated by the fact that line constants calculated using each of these different approaches are not exactly identical. Since transmission lines traverse long distances, it was suspected that these seemingly minor differences can affect accuracy of fault location estimates. Therefore this paper aims to study the impact of line constants calculated using different earth return models on impedance-based fault location algorithms. Analysis was conducted on four actual fault events. For a fault located 14.37 miles from substation, variation between location estimates using each of the three earth models was observed to be within 1%. The paper therefore recommends using any of the three earth models for fault location without significant variation in accuracy.

[1]  William Kersting,et al.  Distribution System Modeling and Analysis , 2001, Electric Power Generation, Transmission, and Distribution: The Electric Power Engineering Handbook.

[2]  J. Horak Zero sequence impedance of overhead transmission lines , 2006, 59th Annual Conference for Protective Relay Engineers, 2006..

[3]  R. Horton,et al.  Effect of line modeling methods on neutral-to-earth voltage analysis of multi-grounded distribution feeders , 2011, 2011 IEEE/PES Power Systems Conference and Exposition.

[4]  A. Deri,et al.  The Complex Ground Return Plane a Simplified Model for Homogeneous and Multi-Layer Earth Return , 1981, IEEE Transactions on Power Apparatus and Systems.

[5]  T. Takagi,et al.  Development of a New Type Fault Locator Using the One-Terminal Voltage and Current Data , 1982, IEEE Power Engineering Review.

[6]  Jian Jiang Elevated neutral -to -earth voltage in distribution systems including harmonics , 2006 .