Experimental Study on the Fire Extinguishing Characteristics of Water Mist System

We carried out fire extinguishing experiments with three kinds of water mist nozzle system. Fire extinguishing experiment according to installed nozzle height and fuel pan location was done. And fire extinguishing performance was compared with plain water and foam agent mixed solution. Water mist nozzle height was varied with 4m, 3.5m and 3m and position of fuel fan was varied 0.5m and 1m from the center of water mist nozzle. Foam agent that used in this experiment is 3% type of AFFF (Aqueous Film Forming Foam) solution. Experimental result showed the door opening effect was little. Fire extinguishing performance of foam agent mixture water mist was better than the plain water mist only.