CFD를 이용한 대형매장 냉열원 주변의 공기유동에 관한 연구
暂无分享,去创建一个
This paper performed to predict vertical temperature distribution and air flow near cold heat source in the mass merchandising store. At the height of 150㎝, the vertical air temperature difference between the results of CFD and of measurement field showed 10% near the refrigeration zone and 8.8% near the freezing zone. Therefore, it regarded as appropriate for the using CFD to investigate airflow near the heat sources. The 3 kinds of CFD model were divided by the disposition of diffuser/exhaust and diffuser air temperature. At the refrigeration and freezing zone in the Model 2 and 3, the temperature difference between the front and the back of human model were showed 6.8℃ and 3.9℃ with diffuser air temperature 17℃ and were showed 6.8℃ and 4℃ with diffuser air temperature 19℃.