Measurement and analysis of surface partial discharges at semi-square voltage waveforms

The fast switching in PWM drive applications exerts complex transient stresses on the cable and motors, creating conditions for different partial discharge form initiation. The mechanism of surface PD on dielectric materials (ethylene-propylene rubber and thermosetting insulation) under semi square voltage has been investigated. In the rod-plane electrode arrangement positive polarity PWM-like pulses with variable rise time (800 ns and longer), and frequency (0.1 Hz to 2 kHz) have been used. Experiments show correlation of PD inception voltage and its time range within a semi-square voltage period with slew rate of applied voltage and its switching frequency. Partial discharges appear not only at rising/falling slope of the voltage pulses but also during the voltage plateau, even when the rod electrode potential becomes zero. The main process taking place during surface PD action on insulating materials is the interaction of space charge near the rod electrode with the polarized dielectric. As a result it was revealed that in such conditions PD can occur within a whole period. This phenomenon is relevant to understand the destructive processes in insulating materials under PWM-like pulses action.

[1]  B. Florkowska,et al.  The influence of PWM stresses on degradation processes in electrical insulation systems , 2010, 2010 Annual Report Conference on Electrical Insulation and Dielectic Phenomena.

[2]  Kai Wu,et al.  Effects of discharge area and surface conductivity on partial discharge behavior in voids under square voltages , 2007, IEEE Transactions on Dielectrics and Electrical Insulation.

[3]  S. Grzybowski,et al.  Electrical Aging Phenomena of XLPE and EPR Cable Insulation Energized by Switching Impulses , 2008, 2008 International Conference on High Voltage Engineering and Application.

[4]  A. Cavallini,et al.  A UHF Technique for Advanced PD Measurements on Inverter-Fed Motors , 2008, IEEE Transactions on Power Electronics.

[5]  A. H. Bonnett,et al.  Analysis of the impact of pulse-width modulated inverter voltage waveforms on AC induction motors , 1994, Proceedings of IEEE Pulp and Paper Industry Conference.

[6]  D. Fabiani,et al.  Relation between space charge accumulation and partial discharge activity in enameled wires under PWM-like voltage waveforms , 2004, IEEE Transactions on Dielectrics and Electrical Insulation.

[7]  T. Bengtsson,et al.  Influence of rise time on partial discharge extinction voltage at semi-square voltage waveforms , 2010, IEEE Transactions on Dielectrics and Electrical Insulation.

[8]  J.C.G. Wheeler,et al.  Effects of converter pulses on the electrical insulation in low and medium voltage motors , 2005, IEEE Electrical Insulation Magazine.

[9]  B. Florkowska,et al.  Influence of fast switching phenomena on electrical insulation systems , 2010 .

[10]  E. Persson,et al.  Transient effects in application of PWM inverters to induction motors , 1991, Conference Record of 1991 Annual Pulp and Paper Industry Technical Conference.