Operating theatre ventilation systems and microbial air contamination in total joint replacement surgery: results of the GISIO-ISChIA study.

BACKGROUND Recent studies have shown a higher rate of surgical site infections in hip prosthesis implantation using unidirectional airflow ventilation compared with turbulent ventilation. However, these studies did not measure the air microbial quality of operating theatres (OTs), and assumed it to be compliant with the recommended standards for this ventilation technique. AIM To evaluate airborne microbial contamination in OTs during hip and knee replacement surgery, and compare the findings with values recommended for joint replacement surgery. METHODS Air samplings were performed in 28 OTs supplied with unidirectional, turbulent and mixed airflow ventilation. Samples were collected using passive sampling to determine the index of microbial air contamination (IMA). Active sampling was also performed in some of the OTs. The average number of people in the OT and the number of door openings during the sampling period were recorded. FINDINGS In total, 1228 elective prosthesis procedures (60.1% hip and 39.9% knee) were included in this study. Of passive samplings performed during surgical activity in unidirectional airflow ventilation OTs (U-OTs) and mixed airflow OTs (M-OTs), 58.9% and 87.6% had IMA values >2, respectively. Of samplings performed during surgical activity in turbulent airflow OTs (T-OTs) and in turbulent airflow OTs with the surgical team wearing Steri-Shield Turbo Helmets (TH-OTs), 8.6% and 60% had IMA values ≤ 2, respectively. Positive correlation was found between IMA values and the number of people in the OT and the number of door openings (P < 0.001). In addition, correlation was found between active and passive sampling (P < 0.001). CONCLUSION These findings challenge the belief that unidirectional systems always provide acceptable airborne bacterial counts.

[1]  Janet M. Twomey,et al.  Validation and Verification , 1997 .

[2]  W R Jarvis,et al.  Guideline for prevention of surgical site infection, 1999. Hospital Infection Control Practices Advisory Committee. , 1999, Infection control and hospital epidemiology.

[3]  B Friberg,et al.  Inconsistent correlation between aerobic bacterial surface and air counts in operating rooms with ultra clean laminar air flows: proposal of a new bacteriological standard for surface contamination. , 1999, The Journal of hospital infection.

[4]  O M Lidwell,et al.  Air, antibiotics and sepsis in replacement joints. , 1988, The Journal of hospital infection.

[5]  H. Braband,et al.  General principles and methods , 1968 .

[6]  C Pasquarella,et al.  The index of microbial air contamination. , 2000, The Journal of hospital infection.

[7]  C Pasquarella,et al.  Lack of influence of body exhaust gowns on aerobic bacterial surface counts in a mixed-ventilation operating theatre. A study of 62 hip arthroplasties. , 2003, The Journal of hospital infection.

[8]  R. Ellison Guidelines for the Prevention of Surgical-Site Infection , 2017 .

[9]  Cesira Pasquarella,et al.  [Air microbial sampling: the state of the art]. , 2008, Igiene e sanita pubblica.

[10]  A. Kramer,et al.  Protective effect of HEPA filtered operating room air ventilation with or without laminar airflow on surgical site infections. , 2009, Annals of surgery.

[11]  Y. Drabu,et al.  Importance of air quality and related factors in the prevention of infection in orthopaedic implant surgery. , 1998, The Journal of hospital infection.

[12]  Nhs Estates Ventilation in Healthcare Premises , 1994 .

[13]  L. Cercenelli,et al.  [Cost evaluation of a ventilation system for operating theatre: an ultraclean design versus a conventional one]. , 2004, Annali di igiene : medicina preventiva e di comunita.

[14]  P. Gastmeier,et al.  Influence of laminar airflow on prosthetic joint infections: a systematic review. , 2012, The Journal of hospital infection.

[15]  P. Vitali,et al.  Microbial air monitoring in operating theatres: experience at the University Hospital of Parma. , 2012, The Journal of hospital infection.

[16]  Air sampling in operating theatres. , 1985, The Journal of hospital infection.

[17]  P Borella,et al.  Risk factors for particulate and microbial contamination of air in operating theatres. , 2007, The Journal of hospital infection.

[18]  Henning Rüden,et al.  Operating Room Ventilation With Laminar Airflow Shows No Protective Effect on the Surgical Site Infection Rate in Orthopedic and Abdominal Surgery , 2008, Annals of surgery.

[19]  I. Heyligers,et al.  Dutch guideline on total hip prosthesis , 2011, Acta orthopaedica.

[20]  Magda Diab-Elschahawi,et al.  Impact of different-sized laminar air flow versus no laminar air flow on bacterial counts in the operating room during orthopedic surgery. , 2011, American journal of infection control.

[21]  Silvio Brusaferro,et al.  Prevention of healthcare associated infections: medical and nursing students' knowledge in Italy. , 2014, Nurse education today.