Partial discharge current pulses in SF6 and the effect of superposition of their radiometric measurement

The practical advantages of employing non-contact radio frequency (RF) methods for detecting partial discharges (PDs) in high voltage equipment have led to significant effort being focused on the diagnosis of electrical plants using RF techniques. This has particularly been the case for gas insulated substations, which use sulphur hexafluoride (SF6) as an insulating medium. One of the most important challenges facing RF diagnostics is the problem of relating the RF emissions to some measure of severity of the PD. Previous work has established that the amplitude or energy of RF signals radiated from a PD source is strongly dependent on the rate of change of current in the PD pulse. In this paper, measurements of PD current pulses in SF6 are presented for a point-plane configuration using an extremely wide bandwidth (13 GHz) measurement system. By this means, PD pulse shapes have been recorded with better resolution than has previously been possible and rise times have been measured with a high degree of accuracy. The results show a considerable variation in pulse shape, with the minimum rise time measured being 35 ps. With this high time-domain resolution, we have been able to distinguish features within the PD pulses that will affect the energy of the radiated RF signal. In particular, the current pulses tend to occur in bursts of up to ten individual pulses in as little as 1 ns, which will excite multiple RF signals in rapid succession. The effect of superposition of RF waveforms has been investigated by studying the variation in detected RF energy with respect to the time delay between PD pulses. It was found that when two PDs occur within a short period (< 150 ns) the combined energy of the resulting RF pulse has the potential to vary by ±30% of that resulting from two equivalent PD pulses with a wider pulse spacing ( 150 ns). In terms of a practical monitoring system concerned with order-of-magnitude variations; this is not considered to pose a major problem for the RF technique.

[1]  C. Fletcher,et al.  Underground cable specification advances and installation practices of the largest investor-owned utilities , 2005, IEEE Electrical Insulation Magazine.

[2]  Martin D. Judd,et al.  Partial discharge diagnostics for gas insulated substations , 1995 .

[3]  B. F. Hampton,et al.  A continuous UHF monitor for gas-insulated substations , 1991 .

[4]  Martin D. Judd,et al.  A NEW INTEGRATED DIAGNOSTIC PARTIAL DISCHARGE MONITORING STRATEGY FOR HV PLANT ITEMS: COMBINING UHF COUPLERS AND THE IEC60270 STANDARD , 2005 .

[5]  N. Ari,et al.  Transient Electromagnetic Fields Due to Switching Operations in Electric Power Systems , 1987, IEEE Transactions on Electromagnetic Compatibility.

[6]  O. Farish,et al.  Modelling partial discharge excitation of UHF signals in waveguide structures using Green's functions , 1996 .

[7]  B. Taylor,et al.  CODATA recommended values of the fundamental physical constants: 2006 | NIST , 2007, 0801.0028.

[8]  David Pommerenke,et al.  Numerical modeling of electrostatic discharge generators , 2003 .

[9]  B. F. Hampton,et al.  Diagnostic measurements at UHF in gas insulated substations , 1988 .

[10]  A. G. Sellars,et al.  UHF detection of leader discharges in SF/sub 6/ , 1995 .

[11]  M. Pompili,et al.  PD pulse burst characteristics of transformer oils , 2006, IEEE Transactions on Power Delivery.

[12]  M.D. Judd,et al.  Partial discharge monitoring for power transformer using UHF sensors. Part 2: field experience , 2005, IEEE Electrical Insulation Magazine.

[13]  Martin D. Judd,et al.  High bandwidth measurement of partial discharge current pulses , 1998, Conference Record of the 1998 IEEE International Symposium on Electrical Insulation (Cat. No.98CH36239).

[14]  R. Morrow Theory of positive corona in SF/sub 6/ due to a voltage impulse , 1991 .

[15]  David Pommerenke,et al.  Application of Maxwell solvers to PD propagation. I. Concepts and codes , 2002 .

[16]  Peter J. Mohr,et al.  CODATA Recommended Values of the Fundamental Constants: 1998 , 2000 .

[17]  Brian G. Stewart,et al.  An integrated measurement strategy for simultaneous fault identification: combining the UHF and IEC60270 techniques , 2005 .

[18]  Martin D. Judd Using finite difference time domain techniques to model electrical discharge phenomena , 2000, 2000 Annual Report Conference on Electrical Insulation and Dielectric Phenomena (Cat. No.00CH37132).

[19]  D. Gray,et al.  Using a step recovery diode to generate repeatable pulses for partial discharge simulation , 2005 .

[20]  Martin D. Judd,et al.  Applying UHF partial discharge detection to power transformers , 2002 .

[21]  S. Boggs Electromagnetic Techniques for Fault and Partial Discharge Location in Gas-Insulated Cables and Substations , 1982, IEEE Transactions on Power Apparatus and Systems.

[22]  Martin D. Judd,et al.  Power transformer monitoring using UHF sensors: site trials , 2002, Conference Record of the the 2002 IEEE International Symposium on Electrical Insulation (Cat. No.02CH37316).

[23]  Hugh Rudnick California Crisis Influences Further Reforms in Latin America , 2002, IEEE Power Engineering Review.

[24]  Masayuki Hikita,et al.  Partial discharge measurement in a long distance SF/sub 6/ gas insulated transmission line (GIL) , 1998 .

[25]  Martin D. Judd,et al.  Study on combining UHF techniques with the IEC60270 standard for monitoring partial discharge of HV plant , 2005 .

[26]  Martin D. Judd,et al.  Power transformer monitoring using UHF sensors: installation and testing , 2000, Conference Record of the 2000 IEEE International Symposium on Electrical Insulation (Cat. No.00CH37075).

[27]  R. Morrow,et al.  The theory of positive glow corona , 1997 .

[28]  R Morrow Theory of electrical corona in SF6 , 1996 .

[29]  Hitoshi Okubo,et al.  The relationship between partial discharge current pulse waveforms and physical mechanisms , 2002 .