Performance of a 5 kW hot water driven diffusion absorption chiller

Abstract This paper presents experimental results of a 5 kW Diffusion-Absorption Chiller (DAC). The chiller has been tested at varying inlet generator temperatures, inlet cooling water temperatures and inlet chilled water temperatures. The lowest driving temperature to keep the bubble pump running was about 90 °C with 3.6 kW cooling capacity and chilled water inlet temperature being set at 18 °C. The maximum cooling capacity and COP reached for the DAC was about 4.52 kW and 0.45, respectively. The prototype has demonstrated a good potential for air-conditioning applications, while not requiring electricity internally for its operation and allowing coupling with waste heat or solar thermal collector systems.

[1]  Adnan Sözen,et al.  The effect of ejector on the performance of diffusion absorption refrigeration systems: An experimental study , 2012 .

[2]  J. Lienhard A heat transfer textbook , 1981 .

[3]  Uli Jakob,et al.  Investigations into solar powered diffusion-absorption cooling machines , 2005 .

[4]  M. Ersöz,et al.  Energy and exergy analyses of the diffusion absorption refrigeration system , 2013 .

[5]  Dietrich Schneider,et al.  Control Optimization of Solar Thermally Driven Chillers , 2016 .

[6]  Wei He,et al.  Experimental investigations on the pumping performance of bubble pumps with organic solutions , 2015 .

[7]  Satha Aphornratana,et al.  Investigation of a diffusion absorption refrigerator , 2002 .

[8]  Juan M. Belman-Flores,et al.  Review of diffusion–absorption refrigeration technologies , 2014 .

[9]  Guangming Chen,et al.  A numerical investigation of a diffusion absorption refrigerator operating with the binary refrigerant for low temperature applications , 2011 .

[10]  Avi Levy,et al.  Performance of a set of parallel bubble pumps operating with a binary solution of R134a-DMAC , 2015 .

[11]  C. A. Infante Ferreira,et al.  Solar refrigeration options – a state-of-the-art review , 2008 .

[12]  Avi Levy,et al.  The influence of diffusion absorption refrigeration cycle configuration on the performance , 2007 .

[13]  Juan M. Belman-Flores,et al.  Energetic analysis of a diffusion–absorption system: A bubble pump under geometrical and operational conditions effects , 2014 .

[14]  N. Velázquez,et al.  Energy analysis of a diffusion absorption cooling system using lithium nitrate, sodium thiocyanate and water as absorbent substances and ammonia as the refrigerant , 2013 .

[15]  Uli Jakob,et al.  Simulation and experimental investigation into diffusion absorption cooling machines for air-conditioning applications , 2008 .