Nucleate boiling of FC-72 and HFE-7100 on porous graphite at different orientations and liquid subcooling

Abstract FC-72 and HFE-7100 dielectric liquids are favored for immersion cooling applications of computer chips. This paper reports the results of series of experiments that systematically investigated nucleate boiling of both FC-72 and HFE-710 on a plain porous graphite surface measuring 10 × 10 mm. The obtained values of the nucleate boiling heat transfer coefficient and critical heat flux (CHF), at different surface orientations, 0° (upward facing) to 180° and liquid subcooling up to 30 K are compared. In addition to the absence of temperature excursions prior to boiling incipience, the CHF increases linearly with increased liquid subcooling but at a rate that is ∼10% higher for HFE-7100 than that for FC-72. The CHF for HFE-7100 is typically 10% to 15% higher than that for FC-72, however, the maximum nucleate boiling heat transfer coefficient, occurring at or near the end of the fully developed nucleate boiling region, is ∼57% higher for FC-72 than that for HFE-7100 and increases also linearly with increased liquid subcooling. The CHF correlation developed accounts for the effects of surface characteristics (smooth, porous, or micro-porous), liquid properties and subcooling, and surface inclination and fits present and reported values by other investigators to within ±10%.

[1]  M. Kaviany,et al.  Critical heat flux in thin, uniform particle coatings , 2006 .

[2]  S. M. You,et al.  Effect of Pressure, Subcooling, and Dissolved Gas on Pool Boiling Heat Transfer From Microporous Surfaces in FC-72 , 2003 .

[3]  R. Jaeger,et al.  Ebullition characteristics of an isolated surface microstructure for immersion cooled heat sinks , 2004, IEEE Transactions on Components and Packaging Technologies.

[4]  H. Honda,et al.  Enhanced Boiling of FC-72 on Silicon Chips with Micro-Pin-Fins and Submicron-Scale Roughness , 2002 .

[5]  A. Priarone Effect of surface orientation on nucleate boiling and critical heat flux of dielectric fluids , 2005 .

[6]  Yogendra Joshi,et al.  Boiling Performance of Single-Layered Enhanced Structures , 2005 .

[7]  S. M. You,et al.  Pool Boiling Heat Transfer From Plain and Microporous, Square Pin Finned Surfaces in Saturated FC-72 , 1999, Heat Transfer: Volume 4.

[8]  S. M. You,et al.  Boiling heat transfer phenomena from microporous and porous surfaces in saturated FC-72 , 1997 .

[9]  Mohamed S. El-Genk,et al.  Transient boiling from inclined and downward-facing surfaces in a saturated pool , 1993 .

[10]  Ruey-Hung Chen,et al.  BUBBLE BEHAVIOR AND HEAT TRANSFER MECHANISM IN FC-72 POOL BOILING , 2001 .

[11]  Duu-Jong Lee,et al.  Boiling of methanol and HFE-7100 on heated surface covered with a layer of mesh , 2001 .

[12]  R. Jaeger,et al.  Effect of nucleation site spacing on the pool boiling characteristics of a structured surface , 2006 .

[13]  I. Mudawar,et al.  Orientation effects on pool boiling critical heat flux (CHF) and modeling of CHF for near-vertical surfaces , 1999 .

[14]  S. M. You,et al.  EFFECTS OF HEATER SIZE AND ORIENTATION ON POOL BOILING HEAT TRANSFER FROM MICROPOROUS COATED SURFACES , 2001 .

[15]  S. S. Kutateladze BOILING HEAT TRANSFER , 1961 .

[16]  Duu-Jong Lee,et al.  Pool Boiling of FC-72 and HFE-7100 , 2001 .

[17]  Jung-Yeul Jung,et al.  Effect of surface condition on boiling heat transfer from silicon chip with submicron-scale roughness , 2006 .

[18]  J. L. Parker,et al.  Enhanced boiling of HFE-7100 dielectric liquid on porous graphite , 2005 .

[19]  S. M. You,et al.  Heater Orientation Effects on Pool Boiling of Micro-Porous-Enhanced Surfaces in Saturated FC-72 , 1996 .

[20]  A. Howard,et al.  An analytical model for near-saturated pool boiling critical heat flux on vertical surfaces , 1997 .

[21]  Avram Bar-Cohen,et al.  Combined Pressure and Subcooling Effects on Pool Boiling From a PPGA Chip Package , 1997 .

[22]  M. El-Genk,et al.  Saturation boiling of HFE-7100 from a copper surface, simulating a microelectronic chip , 2003 .

[23]  J. L. Parker,et al.  Enhanced saturation and subcooled boiling of FC-72 dielectric liquid , 2005 .

[24]  T. C. Cheng,et al.  Pool boiling heat transfer on artificial micro-cavity surfaces in dielectric fluid FC-72 , 2006 .

[25]  J. L. Parker,et al.  Pool boiling in saturated and subcooled HFE-7100 dielectric fluid from a porous graphite surface , 2004, The Ninth Intersociety Conference on Thermal and Thermomechanical Phenomena In Electronic Systems (IEEE Cat. No.04CH37543).

[26]  M. El-Genk COMBINED EFFECTS OF SUBCOOLING AND SURFACE ORIENTATION ON POOL BOILING OF HFE-7100 FROM A SIMULATED ELECTRONIC CHIP , 2003 .

[27]  Ohta Haruhiko,et al.  Effect of surface configuration on nucleate boiling heat transfer , 1984 .

[28]  J. L. Parker,et al.  Efficient spreaders for cooling high-power computer chips , 2007 .

[29]  Mohamed S. El-Genk,et al.  Pool boiling in saturated and subcooled HFE-7100 dielectric fluid from a porous graphite surface , 2004 .

[30]  S. M. You,et al.  Enhanced boiling heat transfer from microporous surfaces: effects of a coating composition and method , 1997 .

[31]  S. Gurrum,et al.  Enhanced boiling heat transfer simulation from structured surfaces : Semi-analytical model , 2006 .

[32]  H. Honda,et al.  Effects of Fin Geometry on Boiling Heat Transfer from Silicon Chips with Micro-Pin-Fins Immersed in FC-72 , 2003 .

[33]  I. Mudawar,et al.  Enhancement of boiling heat transfer using highly wetting liquids with pressed-on fins at low contact forces , 1997 .

[34]  J. L. Parker,et al.  Effect of Surface Orientation on Nucleate Boiling of FC-72 on Porous Graphite , 2006 .