Indoor temperatures for calculating room heat loss and heating capacity of radiant heating systems combined with mechanical ventilation systems

Abstract In this study, a typical office room with a radiant heating system and a mechanical ventilation system was selected as the research subject. Indoor temperature formulas for calculating the room heat loss (including transmission heat loss and ventilation heat loss) and heating capacity of the hybrid system were determined according to the principle of heat transfer. A model to predict indoor temperatures in the room was proposed, and it was determined that the predicted indoor temperatures agreed well with the measured data. Qualitative analyses of the effects of heated surface temperature and air change rates on the indoor temperatures were performed using the proposed model. When heated surface temperatures and air change rates were from 21.0 to 29.0 °C and from 0.5 to 4.0 h −1 , the indoor temperatures for calculating the transmission heat loss and ventilation heat loss were between 20.0 and 20.3 °C and between 19.6 and 20.5 °C, respectively, and the indoor temperature for calculating the heating capacity of the hybrid system was between 18.2 and 19.8 °C. Accordingly, the relative calculation errors were between 0.3% and 0.5% and between −10.2% and 11.8% for calculating the transmission heat loss and ventilation heat loss, respectively, and between 16.0% and 17.4% for calculating the heating capacity of the hybrid system. Due to large relative calculation errors, it is necessary to consider the effect of heated surface and cool supply air on indoor temperatures for calculating ventilation heat loss and heating capacity of radiant heating systems combined with mechanical ventilation systems.

[1]  Bjarne W. Olesen,et al.  Low temperature heating and high temperature cooling , 2009 .

[2]  Tao Zhang,et al.  Temperature and Humidity Independent Control (THIC) of Air-conditioning System , 2014 .

[3]  Francesco Causone,et al.  Experimental Study of Air Distribution and Ventilation Effectiveness in a Room with a Combination of Different Mechanical Ventilation and Heating/Cooling Systems , 2011 .

[4]  M G Apte,et al.  Indoor air quality, ventilation and health symptoms in schools: an analysis of existing information. , 2003, Indoor air.

[5]  Richard D. Watson,et al.  Radiant Heating and Cooling Handbook , 2008 .

[6]  B. Olesen,et al.  Experimental evaluation of heat transfer coefficients between radiant ceiling and room , 2009 .

[7]  Bjarne W. Olesen,et al.  Heat exchange coefficient between floor surface and space by floor cooling -- Theory or a question of definition , 2000 .

[8]  Francesco Causone,et al.  Floor Heating with Displacement Ventilation: An Experimental and Numerical Analysis , 2010 .

[9]  Daniel E. Fisher,et al.  Convective heat transfer in building energy and thermal load calculations , 1997 .

[10]  Standard Ashrae Thermal Environmental Conditions for Human Occupancy , 1992 .

[11]  H. Awbi,et al.  Natural convection from heated room surfaces , 1999 .

[12]  K. S. Chapman,et al.  Impact of heating systems and wall surface temperatures on room operative temperature fields , 2000 .

[13]  Bjarne W. Olesen,et al.  Radiant Floor Heating In Theory and Practice , 2002 .

[14]  Xiaozhou Wu,et al.  A nodal model to predict vertical temperature distribution in a room with floor heating and displacement ventilation , 2013 .

[15]  Francesco Causone,et al.  Floor heating and cooling combined with displacement ventilation: Possibilities and limitations , 2010 .

[16]  Yi Wang,et al.  Ventilation system type, classroom environmental quality and pupils' perceptions and symptoms , 2014 .