급전선로에 설치되어 있는 피뢰기의 누설전류 측정과 관리방안

This paper describes the measurement result of leakage current flowing arresters connected in feeder lines to propose an optimal management method. Twenty seven arresters set in seven areas were analyzed on a regular basis for 4 months. The results showed that the RMS and the peak value of the total leakage currents for soundness arresters were a range of ... respectively. During the period of measurement, the magnitude of the leakage current didn't show conspicious changes and there were impossible places to analyze arrester's status due to including high THD rate in a feeder line. From the study, leakage current measurement has to be performed at a condition without running an electric train in the line, and the allowable RMS value of soundness arrester is bellow 600uA.