An inrush current elimination technique for a voltage sag compensator while powering transformer-coupled loads

Sags are the foremost power quality problem encountered by industrial consumers since they frequently causes the interruption of manufacturing processes that can result in significant economic loss. To resolve such problems, a voltage sag compensator is often installed by industrial consumers within critical industrial applications. However, the operation of the compensator takes a few milliseconds when a sag occurs. Hence the transformer, which is usually mounted in front of the critical load, is likely to be exposed to the sag voltages during this time interval. As a result, when the compensator reinstates the load voltage, a serious magnitude of transient current starts flowing towards the sensitive load. This inrush current can either damage the equipment or activate the protective devices of the compensator. In either case, compensation will eventually fail. To eliminate the inrush current phenomenon and to obtain seamless compensation for sensitive loads, this paper proposes a sag compensator based upon a customary current regulated voltage source inverter (CRVSI). This compensator employs a current control scheme implemented in a stationary frame of reference to regulate the current for the load by connecting it to the secondary of the load transformer. The operation of the proposed system is validated through laboratory test results obtained during different possible sag types.

[1]  T.H. Ortmeyer,et al.  Improved motor starting capability of three phase UPS inverters , 2004, 2004 11th International Conference on Harmonics and Quality of Power (IEEE Cat. No.04EX951).

[2]  Gene F. Franklin,et al.  Digital control of dynamic systems , 1980 .

[3]  Prasad N. Enjeti,et al.  DSP control of high-power UPS systems feeding nonlinear loads , 1996, IEEE Trans. Ind. Electron..

[4]  D. D. Sabin,et al.  An assessment of distribution system power quality. Volume 3: The library of distribution system power quality monitoring case studies , 1996 .

[5]  Po-Tai Cheng,et al.  An Inrush Current Mitigation Technique for the Line-Interactive Uninterruptible Power Supply Systems , 2008, 2008 IEEE Industry Applications Society Annual Meeting.

[6]  Gene F. Franklin,et al.  Digital Control Of Dynamic Systems 3rd Edition , 2014 .

[7]  J. Nevelsteen,et al.  Starting of large motors-methods and economics , 1988, Record of Conference Papers., Industrial Applications Society 35th Annual Petroleum and Chemical Industry Conference,.

[8]  D. G. Holmes,et al.  Improved Stationary Frame AC Current Regulation using Feedforward Compensation of the Load EMF , 2009, 2009 Twenty-Fourth Annual IEEE Applied Power Electronics Conference and Exposition.

[9]  I. Cadirci,et al.  Performance optimization of induction motors during Voltage-controlled soft starting , 2004, IEEE Transactions on Energy Conversion.