Case studies of factors influencing frequency response analysis measurements and power transformer diagnostics

In this article, changes in FRA signatures due to changes in temperature of transformers and in the moisture content of their insulation have been presented and discussed. In the authors' experience, changes in FRA signatures as a result of changes in transformer temperature and moisture content follow a common pattern, independent of the type of winding. However, the magnitude of the changes depends on the transformer type and the complexity of its windings and insulation. The change in FRA signature as a result of mechanical displacement of the windings would follow a different pattern, depending on the nature of the displacement and the winding arrangement. Further study is needed to quantify the dependence of FRA signatures and the insulation properties ε(ω), Z(ω), and Y(ω) on insulation condition (temperature, WCP, aging) in the high frequency range of up to 10 MHz. This may result in the development of a new approach to characterization and assessment of transformer insulation.

[1]  Gang Liu,et al.  Transformer Winding Deformation Diagnosis Using Middle Band Frequency Response Analysis , 2007, 2007 IEEE International Conference on Solid Dielectrics.

[2]  D.M. Sofian,et al.  Interpretation of Transformer FRA Responses— Part I: Influence of Winding Structure , 2009, IEEE Transactions on Power Delivery.

[3]  J. Pleite,et al.  Power transformer core fault diagnosis using frequency response analysis , 2006, MELECON 2006 - 2006 IEEE Mediterranean Electrotechnical Conference.

[4]  Alexander Mamishev,et al.  Moisture equilibrium in transformer paper-oil systems , 1999 .

[5]  S.M. Gubanski,et al.  Exploring possibilities for characterization of power transformer insulation by frequency response analysis (FRA) , 2006, IEEE Transactions on Power Delivery.

[6]  M. de Nigris,et al.  APPLICATION OF MODERN TECHNIQUES FOR THE CONDITION ASSESSMENT OF POWER TRANSFORMERS , 2004 .

[7]  N. Abeywickrama,et al.  Effect of Core Magnetization on Frequency Response Analysis (FRA) of Power Transformers , 2008, IEEE Transactions on Power Delivery.

[8]  A.J. Vandermaar,et al.  Transformer winding movement monitoring in service - key factors affecting FRA measurements , 2004, IEEE Electrical Insulation Magazine.

[9]  N. Abeywickrama,et al.  High-Frequency Modeling of Power Transformers for Use in Frequency Response Analysis (FRA) , 2008, IEEE Transactions on Power Delivery.

[10]  Christos Christopoulos Principles and Techniques of Electromagnetic Compatibility , 2007 .

[11]  Z.D. Wang,et al.  Winding movement in power transformers: a comparison of FRA measurement connection methods , 2006, IEEE Transactions on Dielectrics and Electrical Insulation.

[12]  H. Borsi,et al.  Assessment of Drying Quality for Power Transformer during Manufacturing Process Using Variation of Transfer Function , 2006, 2006 IEEE Conference on Electrical Insulation and Dielectric Phenomena.

[13]  Z.D. Wang,et al.  Investigations on sensitivity of FRA technique in diagnosis of transformer winding deformations , 2004, Conference Record of the 2004 IEEE International Symposium on Electrical Insulation.

[14]  Birgitte Bak-Jensen,et al.  Detection of faults and ageing phenomena in transformers by transfer functions , 1995 .

[15]  O. Moreau,et al.  FRA diagnosis method: simulation applied to feasibility study and efficiency improvement , 1999, IEEE Power Engineering Society. 1999 Winter Meeting (Cat. No.99CH36233).

[16]  T. Leibfried,et al.  Monitoring of power transformers using the transfer function method , 1999 .

[17]  P.T.M. Vaessen,et al.  A new frequency response analysis method for power transformers , 1992 .