The air velocity in the animal occupied zone (AOZ) of a pig facility influences the thermal comfort of pigs and
is affected by the ventilation system in the building. Little is known about the relationship between the air velocity in the AOZ
and the ventilation system design. This article describes the development and a practical test of an air velocity measuring
system in the AOZ using ultrasonic anemometers.
The anemometers were protected by a wire protection cage, which resulted in a lower air velocity measurement that was
corrected by a linear correction factor of 0.83. A suitable aggregation interval for time–averaged air velocity measurements
in occupied pens was 300 s. The effect of animal activity on the measured air velocity was minimal and therefore neglected,
but the location of the anemometer in a pen was deemed important. A representative location was above the resting place
of the animals over the solid floor. The presence of an anemometer in a pen resulted in some minor changes in the lying
behavior of the animals.
In the experimental door–ventilated room with weaned piglets there was a clear (0.04 m/s) and significant difference in
average air velocity between pens 3 and 9 (P < 0.001). The maximum air velocity of 0.15 m/s advised was exceeded in 21%
of the time a pen in the back of the room. In a pen closer to the door, air velocities appeared to be too high less than 2% of
the time.
The measuring system described in this article can be combined with air quality and temperature measurements in the AOZ
for determination of the performance of ventilation systems and comparison of ventilation systems.
[1]
J. M. Randall,et al.
Selection of piggery ventilation systems and penning layouts based on the cooling effects of air speed and temperature
,
1980
.
[2]
D. G. Watts,et al.
Spectral analysis and its applications
,
1968
.
[3]
C. R. Boon,et al.
Measurements of the Effect of Animals on Airflow in an Experimental Piggery
,
1999
.
[4]
Kjeld Svidt,et al.
Measurement and Simulation of Three-Dimensional Airflow in a Livestock Test Room with Two-Dimensional Boundary Conditions
,
1999
.
[5]
Yuanhui Zhang,et al.
Commissioning Livestock Buildings: The Needs and Challenges
,
2000
.
[6]
Sue J. Welham,et al.
Genstat 5 release 3 reference manual
,
1994
.
[7]
S. Hoff.
Isothermal Airflow Characteristics in the Animal-occupied Zone of a Slot-ventilated Swine Facility
,
1995
.
[8]
A.J.A. Aarnink,et al.
AMMONIA VOLATILIZATION AND DUST CONCENTRATION AS AFFECTED BY VENTILATION SYSTEMS IN HOUSES FOR FATTENING PIGS
,
1997
.
[9]
A. V. van Wagenberg,et al.
CONTAMINANT AND HEAT REMOVAL EFFECTIVENESS OF THREE VENTILATION SYSTEMS IN NURSERY ROOMS FOR PIGS
,
2002
.
[10]
C. R. Boon,et al.
Comparison of Predicted and Measured Air Flow Patterns in a Mechanically Ventilated Livestock Building without Animals
,
1997
.
[11]
Kjeld Svidt,et al.
SE—Structures and Environment: The Effects of Pen Partitions and Thermal Pig Simulators on Airflow in a Livestock Test Room
,
2000
.