지휘소 작전지속성 보장을 위한 도파관의 전자기파 차폐성능 향상방안
暂无分享,去创建一个
The stable fueling and water supply should be prerequisites to guarantee the operational sustainment of military command post. Meanwhile, in terms of the operational sustainment, it is verified that the current wave-guided below cutoff (WBC) system cannot satisfy the requirement of control associated with water supply and fueling within the command post. In this study, as the dielectric substance can block electromagnetic pulse (EMP), it was tried to identify the shielding effectiveness of the multi WBCs filled with water and diesel for attenuating the EMP effect using experiment based on the MIL STD 188-125-1. According to the experimental results, used water in the experiment show the shielding effectiveness from around 640 MHz frequency because of minerals contained in the water. Furthermore, it was noted that EMP attenuating strength of the WBC filled with diesel was enlarged from around 1,680 MHz frequency. Resultingly, it could be concluded that it is enough to supply stable water and diesel through the multi WBC to block EMP within the military command post for guaranteeing the military operations sustainment.