Performance analysis of the air-conditioning system in Xi’an Xianyang International Airport

Abstract Reducing the energy consumption of air-conditioning systems is becoming increasingly important. This paper focuses on the air-conditioning system in Terminal 3 in Xi’an Xianyang International Airport, the first airport terminal to adopt radiant cooling in China. In the large spaces of this airport terminal, a temperature and humidity independent control (THIC) system has been adopted instead of a conventional nozzle air supply method, which significantly reduces the energy consumption of the air supply. The radiant floor is the main mechanism for indoor temperature control, while a liquid desiccant outdoor air processor combined with displacement ventilation is responsible for humidity control. Ice storage is adopted to reduce operating costs, and the supplied chilled water temperature can be as low as 3 °C. This paper examines the performance of the THIC system in detail. The indoor environment is determined through measurements to be comfortable, and the on-site performances of key components in both the airport terminal and the cooling plant are investigated. The outdoor air processor supplies air of appropriate temperature and humidity ratio; two kinds of radiant floors are used for temperature control, both with measured cooling capacities of about 30–40 W/m2; and the energy efficiency ratio (EER) of the cooling plant is 2.62.

[1]  Kang Zhao,et al.  Performance of temperature and humidity independent control air-conditioning system in an office bui , 2011 .

[2]  Xiao Feng,et al.  Cumulative exergy analysis of ice thermal storage air conditioning system , 2012 .

[3]  K. F. Fong,et al.  Solar hybrid cooling system for high-tech offices in subtropical climate – Radiant cooling by absorption refrigeration and desiccant dehumidification , 2011 .

[4]  Wen-Shing Lee,et al.  Optimization for ice-storage air-conditioning system using particle swarm algorithm , 2009 .

[5]  Asfaw Beyene,et al.  A comparison of the field performance of thermal energy storage (TES) and conventional chiller systems , 1994 .

[6]  Yi Jiang,et al.  In situ performance of independent humidity control air-conditioning system driven by heat pumps , 2010 .

[7]  경대호,et al.  Radiant Floor Cooling Systems , 2008 .

[8]  Chen Huang,et al.  Measurements of indoor thermal environment and energy analysis in a large space building in typical seasons , 2007 .

[9]  K. Ohtaka,et al.  Measurement and evaluation of the indoor thermal environment in a large domed stadium , 2000 .

[10]  Sih-Li Chen,et al.  Optimization of an ice-storage air conditioning system using dynamic programming method , 2005 .

[11]  Jianlei Niu,et al.  Energy savings potential of chilled-ceiling combined with desiccant cooling in hot and humid climates , 2002 .

[12]  Jacques Miriel,et al.  Radiant ceiling panel heating–cooling systems: experimental and simulated study of the performances, thermal comfort and energy consumptions , 2002 .