Steep-front impulse voltage in diagnostic studies of composite insulators

Laboratory studies of composite insulators by means of steep-front impulse voltage tests are presented. The tests were performed on four groups of insulators, i.e. on newly manufactured insulators, on insulators removed from service, on insulators earlier exposed to mechanical fatigue test and on insulators with intentionally introduced technological defects. Extensive results of these investigations indicate that application of steep-front impulses of 4 kV/ns provides a better diagnostic efficiency as compared with the standard testing by means of impulses with steepness of 1 kV/ns. It is shown that the application of 4 kV/ns impulses do not cause any damage to healthy insulators, while defected insulators are identified reliably. A new methodology allowing to assess the status of internal insulation in insulators removed from service is proposed based on the performed studies.

[1]  M. Kumosa,et al.  Failure analyses of nonceramic insulators: part II - the brittle fracture model and failure prevention , 2005, IEEE Electrical Insulation Magazine.

[2]  Wang Qingxia,et al.  Research of steep-front wave impulse voltage test effectiveness in finding internal fault of composite insulators , 2001, 2001 Annual Report Conference on Electrical Insulation and Dielectric Phenomena (Cat. No.01CH37225).

[3]  Janusz. Fleszyński,et al.  Steep-front impulse voltage tests of composite insulators / , 2003 .

[4]  G. G. Stokes "J." , 1890, The New Yale Book of Quotations.

[5]  M. Kumosa,et al.  Failure analyses of nonceramic insulators. Part 1: Brittle fracture characteristics , 2005, IEEE Electrical Insulation Magazine.

[6]  R. Tripathi,et al.  Electrical degradation of 15 kv composite insulator under accelerated aging conditions , 2013, 2013 IEEE Electrical Insulation Conference (EIC).