Power factor correction for thyristor equipment in the glass industry
暂无分享,去创建一个
Thyristor power controllers are now widely used in the glass industry for controlling furnace temperature. While offering a number of operational advantages, they operate at lagging power factors, which require correction for minimum power cost. Harmonic resonances with the utility feed, however, complicate the use of capacitor banks. The nature of harmonic problems is described and the use of inductors to tune capacitor banks below any possible harmonic frequency is demonstrated. An example design procedure is covered. >
[1] Donald F. Miller. Application Guide for Shunt Capacitors on Industrial Distribution Systems at Medium Voltage Levels , 1976, IEEE Transactions on Industry Applications.
[2] R. P. Stratford,et al. Reactive Compensation and Harmonic Suppression for Industrial Power Systems Using Thyristor Converters , 1976, IEEE Transactions on Industry Applications.