EEI-Manufacturers 500/550 KV Cable Research Project. Cable B-High Pressure Oil Paper Pipe Type
暂无分享,去创建一个
A 550 Kv. paper insulated pipe cable is on test. Maximum stress is 425 v/mil (17 kv/cm). A semi-synthetic taped joint operates at 315 v/mil and dissipation factor about 40% lower than the cable. A telemetered temperature monitoring system gives a direct reading of average conductor temperature. Design and manufacturing details are given.
[1] C. S. Schifreen,et al. Charging Current Limitations in Operation or High-Voltage Cable Lines [includes discussion] , 1956, Transactions of the American Institute of Electrical Engineers Part III Power Apparatus and Systems.
[2] F. H. Buller,et al. The thermal resistance between cables and a surrounding pipe or duct wall , 1950, Transactions of the American Institute of Electrical Engineers.