Implementation of a cascade D-STATCOM under unbalanced conditions

This paper presents a control strategy of star-connected cascade distribution static synchronous compensators (D-STATCOMs) operating under unbalanced conditions. By equivalent transformation, an accurate abc-frame mathematical model of the cascade D-STATCOM with unknown disturbances and parametric perturbation is proposed. Then a novel robust control with L2-gain performance based on the combination with repetitive control and passivity-based control is used to realize the reference current tracking control, where repetitive control is used to compensate the periodic disturbances, and the passivity-based control is used to guarantee the convergence of repetitive control and asymptotic tracking of the control objectives, as well as compensate the influence of aperiodic disturbances on the control performance. The dc voltage control consists of three layers, in which the first layer is realized by injecting a positive-sequence active current, the second by injecting a zero-sequence voltage, and the third based on the active power exchange among H-bridge modules. The effectiveness and performance of this control strategy is verified by simulation and has been tested on a practical installation and operation of ±5 MVAR, 10-kV cascade D-STATCOM.

[1]  Robert H. Lasseter,et al.  Statcom controls for operation with unbalanced voltages , 1998 .

[2]  T. Ise,et al.  Control Scheme of Cascaded H-Bridge STATCOM Using Zero-Sequence Voltage and Negative-Sequence Current , 2010, IEEE Transactions on Power Delivery.

[3]  Liu Hui-jin A Novel L_2-Gain Repetitive Control Algorithm for Single-Phase Active Power Filter , 2008 .

[4]  Yin Chenxu Robust L_2 Performance Criteria Design for Cascade D-STATCOM , 2011 .

[5]  Yang Xiu-yuan Power Control of Three-phase Boost-type PWM Rectifier Based on Passivity , 2008 .

[6]  R.E. Betz,et al.  Symmetry Compensation using a H-Bridge Multilevel STATCOM with Zero Sequence Injection , 2006, Conference Record of the 2006 IEEE Industry Applications Conference Forty-First IAS Annual Meeting.

[7]  P. Mattavelli,et al.  Reactive power and unbalance compensation using STATCOM with dissipativity-based control , 2000, Conference Record of the 2000 IEEE Industry Applications Conference. Thirty-Fifth IAS Annual Meeting and World Conference on Industrial Applications of Electrical Energy (Cat. No.00CH37129).

[8]  Zha Zhipeng Passivity-based Control of Cascade D-STATCOM , 2011 .

[9]  B. Blazic,et al.  Improved D-StatCom control for operation with unbalanced currents and voltages , 2006, IEEE Transactions on Power Delivery.

[10]  Igor Papic,et al.  A new mathematical model and control of D-StatCom for operation under unbalanced conditions , 2004 .

[11]  Zhang Quan-ming A Novel Passivity-Based Control Algorithm for Single-Phase Active Power Filter Using Euler-Lagrange Model , 2008 .

[12]  Paolo Mattavelli,et al.  Reactive power and imbalance compensation using STATCOM with dissipativity-based control , 2001, IEEE Trans. Control. Syst. Technol..

[13]  Wenhua Liu,et al.  Control of a Cascade STATCOM With Star Configuration Under Unbalanced Conditions , 2009 .