Modeling of a Power Transformer Winding for Deformation Detection Based on Frequency Response Analysis

The paper presents a mathematical model of disc-type power transformer winding for frequency response analysis (FRA) based on traveling wave and multiconductor transmission line theories. Each disc of the model is described by traveling wave equations, which are connected to each other in a form of multiconductor transmission line model. The model is applied to FRA simulation in order to study winding axial and radial deformation and its delectability. Comparison of the simulated winding deformation cases with the reference FRA traces is given and discussed to explore the potentials of the proposed model for winding fault detection.

[1]  Reinhold Rüdenberg Electrical Shock Waves in Power Systems: Traveling Waves in Lumped and Distributed Circuit Elements , 1968 .

[2]  Q. H. Wu,et al.  TRANSFER FUNCTION OF TRANSFORMER WINDING FOR FREQUENCY RESPONSE ANALYSIS BASED ON TRAVELING WAVE THEORY , 2006 .

[3]  Guishu Liang,et al.  Modeling of Transformer Windings Under Very Fast Transient Overvoltages , 2006, IEEE Transactions on Electromagnetic Compatibility.

[4]  Peter Crossley,et al.  Simulation of a transformer winding for partial discharge propagation studies , 2002, 2002 IEEE Power Engineering Society Winter Meeting. Conference Proceedings (Cat. No.02CH37309).

[5]  S. A. Ryder,et al.  Diagnosing transformer faults using frequency response analysis , 2003 .

[6]  K. Feser,et al.  Transfer Function Method to Diagnose Axial Displacement and Radial Deformation of Transformer Winding , 2002, IEEE Power Engineering Review.

[7]  T. Sarkar,et al.  Analysis of Multiconductor Transmission Lines , 1988, 31st ARFTG Conference Digest.

[8]  Clayton R. Paul,et al.  Analysis of Multiconductor Transmission Lines , 1994 .

[9]  K. J. Cornick,et al.  A Computer Model for Calculating Steep-Fronted Surge Distribution in Machine Windings , 1989, IEEE Power Engineering Review.

[10]  Z.D. Wang,et al.  Investigations on sensitivity of FRA technique in diagnosis of transformer winding deformations , 2004, Conference Record of the 2004 IEEE International Symposium on Electrical Insulation.

[11]  Guishu Liang,et al.  Analysis of resonance in transformer windings under very fast transient overvoltages , 2006, 2006 17th International Zurich Symposium on Electromagnetic Compatibility.

[12]  A.J. Vandermaar,et al.  Improved detection of power transformer winding movement by extending the FRA high frequency range , 2005, IEEE Transactions on Power Delivery.

[13]  D. J. Wilcox,et al.  Calculation of self and mutual impedances between sections of transformer windings , 1989 .