The Use of Voltage Transformers for the Measurement of Power System Subharmonics in Compliance With International Standards

The measurement of subharmonics in distribution systems requires instrument transformers to reduce voltage and current to levels fitting with the low-voltage input of the power quality (PQ) instruments. The in-force international standards establish algorithms and methods for detecting, measuring, and reporting subharmonics. In particular, the IEC 61000-4-7 suggests performing the discrete Fourier transform over basic time frames of ten cycles (12 cycles) for the 50-Hz (60 Hz) power frequency. Considering the case of 50-Hz constant power frequency, the spectral analysis is performed with a fixed spectral resolution of 5 Hz; thus, subharmonics with a frequency not integer multiple of 5 Hz could introduce inaccuracies in the measurements because of the spectral leakage. In this framework, this article investigates the additional error contributions that can be introduced by voltage transformers (VTs) used, at the input of PQ instruments, to measure subharmonics in compliance with international standards. The analysis is conducted through numerical simulations and experimental tests on two commercial VTs based on different operating principles. Results show that the use of a VT to measure subharmonics, in compliance with international standards, could introduce higher additional errors compared to the ratio errors of the same device evaluated at subharmonic frequencies.

[1]  D. Morinigo-Sotelo,et al.  Analysis of the use of the Hanning Window for the measurement of interharmonic distortion caused by close tones in IEC standard framework. , 2022, Electric Power Systems Research.

[2]  Carmine Landi,et al.  Instrument Transformers for Power Quality Measurements: a Review of Literature and Standards , 2021, 2021 IEEE 11th International Workshop on Applied Measurements for Power Systems (AMPS).

[3]  M. Faifer,et al.  Compensating Nonlinearities in Voltage Transformers for Enhanced Harmonic Measurements: The Simplified Volterra Approach , 2021, IEEE Transactions on Power Delivery.

[4]  H.E. van den Brom,et al.  Measurement Methods and Procedures for Assessing Accuracy of Instrument Transformers for Power Quality Measurements , 2020, 2020 Conference on Precision Electromagnetic Measurements (CPEM).

[5]  Chang Liu,et al.  Research on Simulation Accuracy of Ultra-low Frequency Oscillation in Power System with High Proportion of Hydropower , 2019, 2019 IEEE 3rd International Electrical and Energy Conference (CIEEC).

[6]  S. Perera,et al.  Methods for Harmonic Analysis and Reporting in Future Grid Applications , 2017, IEEE Transactions on Power Delivery.

[7]  A. Testa,et al.  On the interharmonic emission of PV inverters under different operating conditions , 2016, 2016 17th International Conference on Harmonics and Quality of Power (ICHQP).

[8]  Lin Cheng,et al.  A Study on The Impact of Wind Farm Spatial Distribution on Power System Sub-Synchronous Oscillations , 2016, IEEE Transactions on Power Systems.

[9]  M. Kaczmarek,et al.  Accuracy of inductive voltage transformer in the presence of voltage high harmonics , 2014, 2014 ICHVE International Conference on High Voltage Engineering and Application.

[10]  P. Schegner,et al.  Influence of instrument transformers on harmonic distortion assessment , 2012, 2012 IEEE Power and Energy Society General Meeting.

[11]  Lorenzo Peretto,et al.  The role of measurements in the smart grid era , 2010, IEEE Instrumentation & Measurement Magazine.

[12]  Tomasz Tarasiuk,et al.  Comparative Study of Various Methods of DFT Calculation in the Wake of IEC Standard 61000-4-7 , 2009, IEEE Transactions on Instrumentation and Measurement.

[13]  Zbigniew Leonowicz,et al.  Power quality in wind power systems , 2009 .

[14]  Tadeusz Lobos,et al.  Measurement of IEC Groups and Subgroups Using Advanced Spectrum Estimation Methods , 2006, IEEE Transactions on Instrumentation and Measurement.

[15]  M.H.J. Bollen,et al.  Estimating Interharmonics by Using Sliding-Window ESPRIT , 2008, IEEE Transactions on Power Delivery.

[16]  J.M.A. Myrzik,et al.  Consequences of poor power quality - an overview , 2007, 2007 42nd International Universities Power Engineering Conference.

[17]  A. Testa,et al.  On the Processing of harmonics and interharmonics: using Hanning window in standard framework , 2004, IEEE Transactions on Power Delivery.

[18]  Wilsun Xu,et al.  Interharmonics: basic concepts and techniques for their detection and measurement , 2003 .

[19]  J. J. Burns,et al.  Impact of cycloconverter harmonics , 1989 .