Development of a 126kV single-break vacuum circuit breaker and type test

High-voltage vacuum circuit breakers in transmission voltage, as their environmental friendly characteristics, are drawing more and more interests all over the world. The objective of this paper is to present experimental results of type-test for a 126kV/40kA-2500A single-break vacuum circuit breaker based on a standard of IEC 62271-100. Two kinds of test circuits were adopted in type tests for the 126kV/40kA-2500A single-break vacuum circuit breaker. One is direct test circuit for test duties such as out of phase making and breaking test duties OP1 and OP2. The other is synthetic circuit for test duties, such as terminal fault test, capacitive current switching test, short-line fault test, out-of -phase test, double earth test and electrical endurance test. Type-test results, for the 126kV vacuum circuit breaker, presented in this paper are as follows: Dielectric test, 230kV 1min power frequency voltage withstand test and lightning impulse voltage withstand test, with 15 times 550kV in both of polarities; Short time withstand current with 4s duration and peak withstand current test with 100kA; Terminal fault test, including test duties: T10, T30, T60, T100s, T100a; Out of phase making and breaking test, including OP1 and OP2; Short-line fault test L90 and L75; Double-earth fault test as well as capacitive current switching tests of class C1 with test duties of LC1, CC1 and LC2, CC2; Electrical endurance tests; And assessment of condition after test with a 80%of dielectric test voltage; Temperature rise test under rated current of 2500A; Mechanical endurance test of class M1. In summary, the 126kV/40kA-2500A single-break circuit breaker passed the type tests.

[1]  Yingsan Geng,et al.  An opening displacement characteristic determined by high-current anode phenomena of vacuum interrupter , 2011, 2011 1st International Conference on Electric Power Equipment - Switching Technology.

[2]  H. C. Karner,et al.  Dielectric strength of double and single-break vacuum interrupters: experiments with real HV demonstration bottles , 2001 .

[3]  H. Okubo,et al.  Development of Electrical Insulation Techniques in Vacuum for Higher Voltage Vacuum Interrupters , 2006, 2006 International Symposium on Discharges and Electrical Insulation in Vacuum.

[4]  Yingsan Geng,et al.  Axial magnetic field strength needed for a 126kV single break vacuum interrupter , 2010, 24th ISDEIV 2010.

[5]  Satoru Yanabu,et al.  Vacuum arc under an axial magnetic field and its interrupting ability , 1979 .

[6]  R. E. Voshall,et al.  Interruption ability of vacuum interrupters subjected to axial magnetic fields , 1972 .

[7]  R. E. Voshall,et al.  The development of a vacuum interrupter retrofit for the upgrading and life extension of 121 kV-145 kV oil circuit breakers , 1991 .

[8]  Li Jin,et al.  Development of High-Voltage Vacuum Circuit Breakers in China , 2007, IEEE Transactions on Plasma Science.

[9]  H. Saitoh,et al.  Research and development on 145 kV/40 kA one break vacuum circuit breaker , 2002, IEEE/PES Transmission and Distribution Conference and Exhibition.

[10]  P. G. Slade,et al.  Advances in material development for high power, vacuum interrupter contacts , 1994 .

[11]  G. Gaudart,et al.  Compact high-voltage vacuum circuit breaker, a feasibility study , 2007, IEEE Transactions on Dielectrics and Electrical Insulation.