Strength Characteristics of Air Gaps Subjected to Interphase Switching Surges
暂无分享,去创建一个
The present philosophy in the selection of phase-to- phase clearances has been examined. On the basis of a number of oscillograms of switching surges in an EHV system, some characteristics of the overvoltage stresses between phases that have not been considered by the interphase testing methods adopted up to now are demonstrated. By means of a series of switching impulse laboratory tests, it has been shown that these characteristics of thephase-to- phase overvoltages cannot be overlooked in assessing the dielectric strength of phase-to-phase air-insulated structures of substations.
[1] T. Udo,et al. Minimum Phase-to-Phase Electrical Clearances for Substations Based on Switching Surges and Lightning Surges , 1966 .
[2] P. L. Bellaschi. Rationalization of Electrical Clearances for Applications at Extra-High Voltages, 230 Kv to 460/500 Kv , 1959, Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems.