Tests for Moment Redistribution in Flat Plates with Different Reinforcement Details according to End and Midspan Moment Distributions
暂无分享,去创建一个
Three interior slab-column connections designed by equal static moments and by different distribution of end and midspan moments were tested. Each test specimen consists of a 4.2 m square slab and a 355 mm square column stub. The slab thickness is 152 mm. Test results showed not only that flat plate systems can undergo considerable redistribution of moments from the uncracked state to final maximum capacity, but also that the distribution of moments is controlled largely by the distribution of reinforcement adopted by the designer. Tests also indicated that the punching shear strength of slabs can be affected by the redistributed moments.