A simplified analytical model to evaluate the impact of radiant heat on building cooling load

Abstract In some building cooling load calculation methods, the conductive heat gain is calculated using the “air-to-air” conduction method in which the effect of radiative heat on the outer surface of external envelopes has been considered (e.g., using the sol-air temperature). However, the effect of the radiative heat on the inner surface is ignored, which results in uncertainty of conductive heat gain calculation and may bring significant errors in cooling load calculation under some particular conditions. This paper presents a simple method to consider the radiative heat on the inner surface of external envelopes for improving the accuracy of the “air-to-air” conduction method. A simplified analytical model is developed for evaluating the impact of inner radiant heat effect on cooling load. Five case studies are conducted in EnergyPlus to validate the model and to assess the radiative heat impact under different conditions. An illustrative example is presented to demonstrate the procedures of using the developed method to evaluate the inner radiation effect in a real building in Hong Kong. It is found that the most important factors determining the inner radiation effect are the radiative heat conditions and the building zoning configurations, and oversimplifying the zoning configuration might result in errors of up to 10% in cooling load calculations.

[1]  Sture Holmberg,et al.  Performance evaluation of radiant baseboards (skirtings) for room heating – An analytical and experimental approach , 2014 .

[2]  Ibrahim Atmaca,et al.  Effects of radiant temperature on thermal comfort , 2007 .

[3]  Fu Xiao,et al.  Quantitative energy performance assessment methods for existing buildings , 2012 .

[4]  Enrico Fabrizio,et al.  Building energy performance assessment through simplified models: Application of the ISO 13790 quasi-steady state method , 2007 .

[5]  Tamami Kusuda NBSLD, the computer program for heating and cooling loads in buildings , 1974 .

[6]  Stanley A. Mumma,et al.  Simplified cooling capacity estimation model for top insulated metal ceiling radiant cooling panels , 2004 .

[7]  Stéphane Bertagnolio,et al.  Radiant ceiling systems coupled to its environment part 2: Dynamic modeling and validation , 2010 .

[8]  Hongxing Yang,et al.  Investigation on the thermal performance of different lightweight roofing structures and its effect on space cooling load , 2009 .

[9]  Abd El-Aziz S. Fouda,et al.  Assessment of a modified method for determining the cooling load of residential buildings , 2010 .

[10]  Daniel E. Fisher,et al.  EnergyPlus: creating a new-generation building energy simulation program , 2001 .

[11]  Francis W.H. Yik,et al.  An evaluation of the appropriateness of using overall thermal transfer value (OTTV) to regulate envelope energy performance of air-conditioned buildings , 2004 .

[12]  Refet Karadağ New approach relevant to total heat transfer coefficient including the effect of radiation and convection at the ceiling in a cooled ceiling room , 2009 .

[13]  Fred Bauman,et al.  Cooling load differences between radiant and air systems , 2013 .

[14]  Baris Burak Kanbur,et al.  Experimental investigation of heat transfer coefficients between hydronic radiant heated wall and room , 2014 .

[15]  Daniel E. Fisher,et al.  Development of a heat balance procedure for calculating cooling loads , 1997 .

[16]  Simon J. Rees,et al.  Quantitative comparison of North American and U.K. cooling load calculation procedures -- Methodology , 1998 .

[17]  K. W. Mui,et al.  Cooling load calculations in subtropical climate , 2007 .

[18]  Zhe Tian,et al.  Establishment and experimental validation of a dynamic heat transfer model for concrete radiant cooling slab based on reaction coefficient method , 2014 .

[19]  Dongliang Zhang,et al.  Experimental and numerical analysis of lightweight radiant floor heating system , 2013 .

[20]  Jeffrey D. Spitler,et al.  The Radiant Time Series Cooling Load Calculation Procedure , 1997 .

[21]  S. F. Bruning A New Way to Calculate Cooling Loads , 2004 .

[22]  Jacques Miriel,et al.  Radiant ceiling panel heating–cooling systems: experimental and simulated study of the performances, thermal comfort and energy consumptions , 2002 .

[23]  Z. Lian,et al.  Distribution ratio of radiant heat and its effect on cooling load , 2003 .

[24]  Celestino R. Ruivo,et al.  Prediction of thermal load temperature difference values for the external envelope of rooms with setback and setup thermostats , 2013 .

[25]  Fu Xiao,et al.  A simplified energy performance assessment method for existing buildings based on energy bill disaggregation , 2012 .

[26]  Li Li,et al.  Experimental study on calculation method of the radiant time factors , 2015 .

[27]  B. Olesen,et al.  Experimental evaluation of heat transfer coefficients between radiant ceiling and room , 2009 .