RC 네트워크 모델 및 유한차분법에 의한 구체축열시스템의 방열량 해석

This study is focused on the evaluation of thermal output of TABS(Thermally Activated Building System) according to the ISO 11855. The aim of this study is to evaluate TABS in terms of the temperature difference between heating medium supply temperature(T s ) and return temperature(T r ), thermal output and the surface temperature distribution according to the design flow rate and the design flow temperature. For this purpose, the RC network model and FDM method in ISO 11855 were firstly reviewed. Through the transient heat transfer simulation using temperature calculation using Cranck-Nicolson FDM using Physibel Voltra 6.0W, the temperature difference between T s and T r , thermal output and the surface temperature distribution of specific TABS was calculated and evaluated. The results show that specific thermal output and temperature difference at 60℃ of supply water temperature were about 162 W/㎡, 13.6℃ respectively.