Experimental study on two-phase separation performance of impacting T-junction

Abstract In this paper, the performance of a vertical impacting T-junction acting as a phase separator for application in thermodynamic cycles was investigated experimentally. The T-junction had a horizontal inlet tube (internal diameter 8.0 mm) and two equal-sized vertical outlet branches (internal diameter 17.5 mm). All experiments were conducted using refrigerant R134a, with inlet mass flux and quality being varied in the range of 100 to 600 kg·m −2 ·s −1 and 0.1 to 0.6, respectively. Flow regimes prior to the T-junction were identified and characterized. Effects of vapor and liquid velocity as well as the opening of control valve on the liquid separation efficiency were investigated. It was found that the separation efficiency deteriorated dramatically as the vapor phase Froude number in the upward tube increased. Liquid falling phenomenon in the upward branch was observed, and a simple correlation between the fraction of falling liquid and the vapor phase Froude number was derived. On the basis of this correlation, modified models for phase separation of annular and stratified-wavy flow in a vertical impacting T-junction were developed. The average absolute deviation between the predicted liquid mass flow ratio at the bottom outlet of the T-junction and those measured values is about 6.4% and 6.9% for annular flow and stratified-wavy flow respectively.

[1]  Keumnam Cho,et al.  Two-phase split of refrigerants at a T-junction , 2006 .

[2]  Annular two-phase flow split at an impacting T , 1987 .

[3]  M. A. Mohamed,et al.  Conditions for complete phase separation in an impacting tee junction at various inclinations of the outlet arms , 2012 .

[4]  Pega Hrnjak,et al.  Enhancement of vapor–liquid separation in vertical impact T-junctions for vapor compression systems with flash gas bypass , 2014 .

[5]  H. M. Soliman,et al.  Experimental investigation of two-phase flow splitting in an equal-sided impacting tee junction with inclined outlets , 2011 .

[6]  Min-Soo Kim,et al.  Experimental study on the performance of a heat pump system with refrigerant mixtures’ composition change , 2004 .

[7]  Robert J. Moffat,et al.  Describing the Uncertainties in Experimental Results , 1988 .

[8]  H. M. Soliman,et al.  Two-phase flow in a horizontal equal-sided impacting tee junction , 2007 .

[9]  Mortaza Yari,et al.  Thermodynamic analysis and optimization of novel ejector-expansion TRCC (transcritical CO2) cascade refrigeration cycles (Novel transcritical CO2 cycle) , 2011 .

[10]  Pega Hrnjak,et al.  Vapor–liquid separation in a vertical impact T-junction for vapor compression systems with flash gas bypass , 2014 .

[11]  Jen-Shih Chang,et al.  Gas‐liquid two‐phase flow in symmetrically dividing horizontal tubes , 1991 .

[12]  M. McLinden,et al.  NIST Standard Reference Database 23: Reference Fluid Thermodynamic and Transport Properties-REFPROP, Version 8.0 , 2007 .

[13]  Reinhard Radermacher,et al.  Transient and steady-state experimental investigation of flash tank vapor injection heat pump cycle control strategy , 2011 .

[14]  Ki C. Hong,et al.  Two-Phase Flow Splitting at an Impacting Tee , 1995 .

[15]  Ralph Greif,et al.  Comparison of the Organic Flash Cycle (OFC) to other advanced vapor cycles for intermediate and high temperature waste heat reclamation and solar thermal energy , 2012 .

[16]  Mariarosa Giardina,et al.  A semi-empirical approach for predicting two-phase flow discharge through branches of various orientations connected to a horizontal main pipe , 2010 .

[18]  J. Thome,et al.  Investigation of Flow Boiling in Horizontal Tubes: Part I, A New Diabatic Two-Phase Flow Pattern Map , 2005 .

[19]  A. Murphy,et al.  Two-Phase Bifurcated Dividing Pipe Flow , 2009 .

[20]  A. Elazhary,et al.  Two-phase flow in a horizontal mini-size impacting T-junction with a rectangular cross-section , 2012 .

[21]  Masahiro Shoji,et al.  Fluctuation characteristics of two-phase flow splitting at a vertical impacting T-junction , 2002 .

[22]  Shuai Deng,et al.  A thermodynamic analysis of an auto-cascade heat pump cycle for heating application in cold regions , 2014 .

[23]  H. M. Soliman,et al.  Effects of pipe size and system pressure on the phase redistribution in horizontal impacting tee junctions , 2014 .

[24]  R. Lahey,et al.  Phase separation in impacting wyes and tees , 1989 .

[25]  J. Thome,et al.  Flow pattern maps for convective boiling of CO2 and R410A in a horizontal smooth tube: Experiments and new correlations analyzing the effect of the reduced pressure , 2012 .

[26]  Predrag Stojan Hrnjak,et al.  Flash gas bypass in mobile air conditioning system with R134a , 2012 .