A new approach for calculating zone-2 setting of distance relays and its use in an adaptive protection system

This paper presents a method for calculating zone-2 setting of distance relays without causing coordination problems. The proposed method is based on the impedance seen by distance relays when faults are simulated on the reach of zone-1 of primary relays for the maximum and minimum generation outputs of the power system. It is shown that the proposed method increases the reach of zone-2 relays without causing coordination problems. The proposed method is modified for use in an adaptive protection system. It is shown that further improvements can be achieved when settings are calculated using the proposed method and the prevailing system conditions. Measures to alleviate the impact of communication failure are discussed. The proposed method and its adaptive version were applied to an existing power system and some results are reported in the paper.

[1]  S. S. Venkata,et al.  Adaptive transmission protection: concepts and computational issues , 1989 .

[2]  M. S. Sachdev,et al.  Topology detection for adaptive protection of distribution networks , 1995, Proceedings 1995 International Conference on Energy Management and Power Delivery EMPD '95.

[3]  Arun G. Phadke,et al.  Adaptive transmission system relaying , 1988 .

[4]  J. R. Linders,et al.  Adaptive transmission relaying concepts for improved performance , 1988 .

[5]  J. Lewis Blackburn,et al.  Protective Relaying: Principles And Applications , 2006 .

[6]  M. S. Sachdev,et al.  Protection of a distribution network: An adaptive approach , 1994, Canadian Journal of Electrical and Computer Engineering.