Coordinated control strategy for UPQC and its verification

This paper researches profoundly on the coordinated control of UPQC (unified power quality conditioner). By analyzing the radical reasons of coupling effect between UPQC series unit and shunt unit, a simple and practical coordinated control strategy for UPQC series unit and shunt unit is proposed, i.e. by introducing corresponding voltage corrective link directly to UPQC series unit and shunt unit respectively, and by suitable mode of PWM in addition, the coupling effect between its series unit and shunt unit is eliminated fully. Therefore, the complex degree of the whole UPQC control system is simplified greatly. Combined with a power quality waveform tracking method based on Hinfin control, the coordinated control between UPQC series unit and shunt unit is implemented by the proposed strategy. The experimental results indicate that the method can eliminate the steady-state phase shift and amplitude attenuation of the voltage tracking compensation of series unit and the current tracking compensation of shunt unit for UPQC. Finally, the unified power quality multi-function control of UPQC is achieved

[1]  Yang Yihan,et al.  A novel control method of power quality waveform tracking compensation based on H/sub /spl infin// model matching technology , 2004, 2004 International Conference on Power System Technology, 2004. PowerCon 2004..

[2]  Wan Jian-ru RESEARCH ON SYNCHRONIZATION DEADBEAT CONTROL ALGORITHM FOR UNIFIED POWER QUALITY CONDITIONER , 2005 .

[3]  Arindam Ghosh,et al.  A unified power quality conditioner (UPQC) for simultaneous voltage and current compensation , 2001 .

[4]  P.L. So,et al.  Unified power quality conditioner for improving power quality using ANN with hysteresis control , 2004, 2004 International Conference on Power System Technology, 2004. PowerCon 2004..

[5]  T. G. Habetler,et al.  Combined deadbeat control of a series-parallel converter combination used as a universal power filter , 1995 .

[6]  Alfred Rufer,et al.  Power quality compensation using universal power quality conditioning system , 2000 .

[7]  Peng Li,et al.  Power Quality Control Center and Its Control Method , 2005, 2005 IEEE/PES Transmission & Distribution Conference & Exposition: Asia and Pacific.

[8]  Malabika Basu,et al.  Experimental investigation of performance of a single phase UPQC for voltage sensitive and non-linear loads , 2001, 4th IEEE International Conference on Power Electronics and Drive Systems. IEEE PEDS 2001 - Indonesia. Proceedings (Cat. No.01TH8594).

[9]  Hirofumi Akagi,et al.  The unified power quality conditioner: the integration of series- and shunt-active filters , 1998 .