International benchmark on the natural convection test in Phenix reactor

Abstract The French Phenix sodium cooled fast reactor (SFR) started operation in 1973 and was stopped in 2009. Before the reactor was definitively shutdown, several final tests were planned and performed, including a natural convection test in the primary circuit. During this natural convection test, the heat rejection provided by the steam generators was disabled, followed several minutes later by reactor scram and coast-down of the primary pumps. The International Atomic Energy Agency (IAEA) launched a Coordinated Research Project (CRP) named “control rod withdrawal and sodium natural circulation tests performed during the Phenix end-of-life experiments”. The overall purpose of the CRP was to improve the Member States’ analytical capabilities in the field of SFR safety. An international benchmark on the natural convection test was organized with “blind” calculations in a first step, then “post-test” calculations and sensitivity studies compared with reactor measurements. Eight organizations from seven Member States took part in the benchmark: ANL (USA), CEA (France), IGCAR (India), IPPE (Russian Federation), IRSN (France), KAERI (Korea), PSI (Switzerland) and University of Fukui (Japan). Each organization performed computations and contributed to the analysis and global recommendations. This paper summarizes the findings of the CRP benchmark exercise associated with the Phenix natural convection test, including blind calculations, post-test calculations and comparisons with measured data. General comments and recommendations are pointed out to improve future simulations of natural convection in SFRs.