Development of Novel 3-Phase Line-interactive UPS System using 4-leg PWM Converter/Inverter and AC Reactor

In this paper a novel line interactive UPS (Uninterruptible Power Supply) using the two 4-leg VSCs and AC line reactor is proposed. The 4-leg Voltage Source Converter(VSC) can use the DC link voltage effectively by the 3-D SVPWM method. Hence the DC battery voltage can be reduced by 15% in comparison to that of the conventional line-interactive UPS system. One VSC is in parallel with the AC line reactor of the power source side, and the other is in series with the load. The parallel 4-leg voltage source inverter controls three-phase line voltage independently in order to control the line reactor current indirectly. It eliminates the neutral line current and the active ripple power of the source side using the pqr theory so that unity power factor and the sinusoidal source current can be achieved even though both the source and the load voltages have zero sequence components. The series 4-leg voltage source inverter compensates the line voltage and allows the load voltage to be balanced and harmonic-free. Both of parallel and series 4-leg voltage source inverters always act as independently controllable voltage sources, so that three-phase output voltage shows a seamless transition to the backup mode. The feasibility of the proposed UPS system has been investigated and verified through computer simulation results.