Abstract Solar absorption cooling systems are available from various reports, in large capacities up to several hundred kilowatts. However, in the range of small capacities ( 2 solar collector arrays, one absorption chiller with a rated cooling capacity of 8 kW, and a hot storage water storage tank of 3 m 3 in volume. The chilled water can be delivered either into fan coils or into radiant cooling panels, which are installed to satisfy the demands of the indoor thermal environment of the test room. As for the fan coil cooling mode, it was found that the average cooling output reached 4.27 kW during 9 h of operation under typical weather conditions for Shanghai. The PMV (predicted mean value, a measure of thermal comfort) inside the test room could be controlled between −0.29 and 0.32. With regard to the radiant cooling mode, an individual supply air unit was installed for the purpose of preventing condensation on the cooling panels. Comparing with the experimental results of the fan coil cooling mode, the average cooling output increased by 23.5%.

[1]  Sirichai Thepa,et al.  Experience with fully operational solar-driven 10-ton LiBr/H2O single-effect absorption cooling system in Thailand , 2008 .

[2]  Ursula Eicker,et al.  Design and performance of solar powered absorption cooling systems in office buildings , 2009 .

[3]  Xiaoqiang Zhai,et al.  Experiences on solar heating and cooling in China , 2008 .

[4]  F. Rosa,et al.  Solar absorption cooling plant in Seville , 2010 .

[5]  Graeme Maidment,et al.  A novel experimental investigation of a solar cooling system in Madrid , 2005 .

[6]  Franck Lucas,et al.  Experimental investigation of a solar cooling absorption system operating without any backup system under tropical climate , 2010 .

[7]  Rabah Gomri,et al.  Second law analysis of double effect vapour absorption cooler system , 2008 .

[8]  Ruzhu Wang,et al.  Solar sorption cooling systems for residential applications: Options and guidelines , 2009 .

[9]  Clemens Pollerberg,et al.  Performance assessment of an integrated free cooling and solar powered single-effect lithium bromide-water absorption chiller , 2008 .

[10]  Francisco J. Batlles,et al.  Integration of the solar thermal energy in the construction: Analysis of the solar-assisted air-conditioning system installed in CIESOL building , 2009 .

[11]  Theocharis Tsoutsos,et al.  Design of a solar absorption cooling system in a Greek hospital , 2010 .

[12]  Xiaoqiang Zhai,et al.  Development of solar thermal technologies in China , 2010 .

[13]  Runsheng Tang,et al.  Solar thermal utilization in China , 2004 .

[14]  Hongbo He,et al.  Modeling of a solar-assisted HVAC system with thermal storage , 2010 .

[15]  X. Zhai,et al.  Solar integrated energy system for a green building , 2007 .

[16]  Francesco Calise,et al.  Thermoeconomic analysis and optimization of high efficiency solar heating and cooling systems for different Italian school buildings and climates , 2010 .

[17]  Daniel E. Fisher,et al.  Energetic, economic and environmental performance of a solar-thermal-assisted HVAC system , 2010 .

[18]  Standard Ashrae Thermal Environmental Conditions for Human Occupancy , 1992 .