A novel nine-switch PWM rectifier-inverter topology for three-phase UPS applications

A novel three-phase PWM rectifier-inverter topology for UPS applications is proposed in this paper. The topology uses only nine IGBT devices for AC/AC conversion through a quasi DC link circuit. This converter topology features sinusoidal inputs and outputs, unity input power factor, and more importantly, low manufacturing cost. The operating principle of the converter is elaborated and a novel modulation scheme is presented. The performance of the proposed converter is verified by experiments on a 5 kVA prototyping UPS system.

[1]  P.F. Seixas,et al.  A three-phase line-interactive UPS system implementation with series-parallel active power-line conditioning capabilities , 2001, Conference Record of the 2001 IEEE Industry Applications Conference. 36th IAS Annual Meeting (Cat. No.01CH37248).

[2]  E.A.A. Coelho,et al.  An online no-break with power factor correction and output voltage stabilization , 2005, IEEE Transactions on Power Electronics.

[3]  Ming Tsung Tsai,et al.  Design and implementation of a cost-effective quasi line-interactive UPS with novel topology , 2003 .

[4]  M. Liserre,et al.  A novel three-phase single-stage distributed power inverter , 2004, IEEE Transactions on Power Electronics.

[5]  Deepak Divan,et al.  Dynamic sag correctors: cost effective industrial power line conditioning , 1999, Conference Record of the 1999 IEEE Industry Applications Conference. Thirty-Forth IAS Annual Meeting (Cat. No.99CH36370).

[6]  T. G. Habetler,et al.  A novel on-line UPS with universal filtering capabilities , 1995 .

[7]  S. Karve,et al.  Three of a kind [UPS topologies, IEC standard] , 2000 .