An on-load tap changer (OLTC) is prone to many different defects and degradation mechanisms due to its continuous operation under load condition. A high load current and high operation temperature accelerate the process of contact wear. Contacts erode due to the fact that under certain conditions the contacts develop a resistive layer due to hot insulation oil. As a major cause of OLTC failure, these defects might take place after some years of operation and their frequency increases with the operation time. Regular maintenance is applied due to degradation of the insulation oil. Dynamic resistance measurement (DRM) can be conducted during this maintenance to measure the resistance of the OLTC when it operates. The measurement results provide important information for assessing the actual condition of the OLTC. This paper aims to analyze the effect of test parameters on DRM results from service-aged OLTCs and describes the implementation of DRM in OLTC condition assessment. Two test parameters were selected for observation: the test current amplitude and the circuit resistance. Their amplitude was varied during laboratory experiments as well as on-site after regular maintenance. To quantify the various measurement results, an analytical tool using 4 performance parameters has been developed. Finally for interpretation, with the help of a three dimensional classification system which is presented in this paper, the actual condition of OLTCs can be identified during maintenance activities.
[1]
E. Gulski,et al.
Advanced on-site diagnosis of transformer on-load tap changer
,
2008,
Conference Record of the 2008 IEEE International Symposium on Electrical Insulation.
[2]
E. Gulski,et al.
Experimental model of aging mechanisms of on-load tap changer contacts
,
2008,
2008 International Conference on Condition Monitoring and Diagnosis.
[3]
E. Gulski,et al.
On-load tap changer diagnosis: Interpretation of dynamic resistance deviations
,
2010,
2010 IEEE International Symposium on Electrical Insulation.
[4]
H.-U. Schellhase,et al.
Load tap changers: investigations of contacts, contact wear and contact coking
,
2002,
Proceedings of the Forty-Eighth IEEE Holm Conference on Electrical Contacts.
[5]
E Gulski,et al.
On-load tap changer diagnosis - an off-line method for detecting degradation and defects: Part 1
,
2010,
IEEE Electrical Insulation Magazine.
[6]
P. J. Griffin,et al.
Artificial intelligence in OLTC fault diagnosis using dissolved gas-in-oil information
,
2000,
2000 Power Engineering Society Summer Meeting (Cat. No.00CH37134).