Principles of loop thermosyphon and its application in data center cooling systems: A review

Abstract With the development of big data and cloud computing technologies, data centers have grown rapidly worldwide. Although the commonly used data center cooling system (computer room air conditioning system, CRAC) is safe and reliable, it has a high energy consumption. Loop thermosyphon consumes less energy than the CRAC system and can be used in data center cooling system. This review presents the operating principles of the loop thermosyphon and its application in a data center cooling system. First, this review introduces the types of heat pipes and the operating principles of the loop thermosyphon. Second, the application of the loop thermosyphon in the room-, rack- and on-chip-level cooling of data center is reviewed. Finally, a combined compressor and loop thermosyphon system is introduced, which can be used to cool telecommunications base station. As the system can use cold ambient air directly as heat sink, it is more energy-efficient in comparison with using air conditioning alone as the cooling method. After reviewed and compared recent articles, we have indicated the imperfect points in recent researches and the future's development trend based on the results of researches and our experience. We think the points of this review is useful to the industrial applications.

[1]  Jinkyun Cho,et al.  Development and experimental study of an independent row-based cooling system for improving thermal performance of a data center , 2020 .

[2]  Hao Tian,et al.  A combined cooling solution for high heat density data centers using multi-stage heat pipe loops , 2015 .

[3]  S. Rittidech,et al.  A correlation to predict heat-transfer rates of a two-phase closed thermosyphon (TPCT) using silver nanofluid at normal operating conditions , 2010 .

[4]  Hamza Salih Erden,et al.  A parametric CFD study of computer room air handling bypass in air-cooled data centers , 2020 .

[5]  Masud Behnia,et al.  Cooling solutions in an operational data centre: A case study , 2011 .

[6]  Quan Zhang,et al.  Experimental study on the thermal characteristics of micro channel separate heat pipe respect to different filling ratio , 2016 .

[7]  Zhang Hainan,et al.  Performance Analysis on Hybrid System of Thermosyphon free Cooling and Vapor Compression Refrigeration for Data Centers in Different Climate Zones of China , 2014 .

[8]  Shizuo Saitoh,et al.  Effect of tube diameter on boiling heat transfer of R-134a in horizontal small-diameter tubes , 2005 .

[9]  Yi Jiang,et al.  Match properties of heat transfer and coupled heat and mass transfer processes in air-conditioning system , 2012 .

[10]  Jian Wang,et al.  Evaluation metrics of thermal management in data centers based on exergy analysis , 2019, Applied Thermal Engineering.

[11]  Saffa Riffat,et al.  Mathematical model of indirect evaporative cooler using porous ceramic and heat pipe , 2004 .

[12]  X. Tian,et al.  Investigation into the energy consumption of a data center with a thermosyphon heat exchanger , 2011 .

[13]  Zhen Li,et al.  Comparison work about different empirical formulas for the boiling heat transfer coefficient in separated heat pipe system , 2019, International Journal of Low-Carbon Technologies.

[14]  Ravi Kumar,et al.  Heat transfer characteristics and flow pattern during two-phase flow boiling of R134a and R407C in a horizontal smooth tube , 2014 .

[15]  Jackson Braz Marcinichen,et al.  Two-Phase Flow Control of Electronics Cooling With Pseudo-CPUs in Parallel Flow Circuits: Dynamic Modeling and Experimental Evaluation , 2013 .

[16]  Jinkyun Cho,et al.  Evaluation of air management system's thermal performance for superior cooling efficiency in high-de , 2011 .

[17]  C. Tian,et al.  Simulation on vertical microchannel evaporator for rack-backdoor cooling of data center , 2020 .

[18]  Zhang Meng,et al.  Effect of raised floor height on different arrangement of under-floor air distribution performance in data center , 2017 .

[19]  José M. Cardemil,et al.  Energy and exergy assessment in a perimeter cooled data center: The value of second law efficiency , 2017 .

[20]  A. Faghri,et al.  Experimental investigation on loop thermosyphon thermal performance with flow visualization , 2020 .

[21]  S. A. Nada,et al.  Effect of CRAC units layout on thermal management of data center , 2017 .

[22]  Hafiz M. Daraghmeh,et al.  A review of current status of free cooling in datacenters , 2017 .

[23]  Wenxing Shi,et al.  A performance evaluation index for two-phase thermosyphon loop used in HVAC systems , 2018 .

[24]  Rahmatollah Khodabandeh Heat transfer in the evaporator of an advanced two-phase thermosyphon loop , 2005 .

[25]  Zhen Li,et al.  Research on the refrigerant column height in the downcomer of a two-phase loop thermosyphon , 2018, International Journal of Refrigeration.

[26]  S. Wongwises,et al.  Evaporation heat transfer and friction characteristics of R-134a flowing downward in a vertical corrugated tube , 2011 .

[27]  K. E. Elfeky,et al.  Experimental study of solving thermal heterogeneity problem of data center servers , 2016 .

[28]  M. El-Genk Immersion cooling nucleate boiling of high power computer chips , 2012 .

[29]  Jia-Xiong Li,et al.  Enhanced immersion cooling using two-tier micro- and nano-structures , 2018 .

[30]  Zhen Li,et al.  Experimental study on a loop thermosyphon cooling system in data centers using CO2 as a working Fluid, especially thermal environment and energy-saving effect , 2020 .

[31]  Guoyuan Ma,et al.  Development and analysis of a pump-driven loop heat pipe unit for cooling a small data center , 2017 .

[32]  Somchai Wongwises,et al.  The difference in flow pattern, heat transfer and pressure drop characteristics of mini-channel flow boiling in horizontal and vertical orientations , 2018 .

[33]  Zhen Li,et al.  Experimental investigations of the influence factors for the boiling heat transfer characteristics of R134a coolant in a loop thermosiphon system , 2020, International Journal of Refrigeration.

[34]  Z. Zhai,et al.  CFD simulation on the heat transfer and flow characteristics of a microchannel separate heat pipe under different filling ratios , 2018, Applied Thermal Engineering.

[35]  J. M. Coulson,et al.  Heat Transfer , 2018, Finite Element Method for Solids and Structures.

[36]  Baolong Wang,et al.  Experimental investigation on two-phase thermosyphon loop with partially liquid-filled downcomer , 2015 .

[37]  Xiaohua Liu,et al.  Experimental study of the self-regulating performance of an R744 two-phase thermosyphon loop , 2017 .

[38]  Zhang Hainan,et al.  Integrated system of mechanical refrigeration and thermosyphon for free cooling of data centers , 2015 .

[39]  Stéphane Le Masson,et al.  Two-phase thermosyphon loop for cooling outdoor telecommunication equipments , 2013 .

[40]  Xiaohua Liu,et al.  Experimental study on the effect of fill ratio on an R744 two-phase thermosyphon loop , 2016 .

[41]  M. Cooper Heat Flow Rates in Saturated Nucleate Pool Boiling-A Wide-Ranging Examination Using Reduced Properties , 1984 .

[42]  C. Yi,et al.  Heat transfer performance analysis of a large-scale separate heat pipe with a built-in tube , 2020 .

[43]  Zhen Li,et al.  Application of separated heat pipe system in data center cooling. , 2016 .

[44]  Chen Wang,et al.  Phase-change immersion cooling high power light emitting diodes and heat transfer improvement , 2017, Microelectron. Reliab..

[45]  Kyung Chun Kim,et al.  Flow boiling characteristics of R134a and R245fa mixtures in a vertical circular tube , 2016 .

[46]  Zhihang Song Numerical cooling performance evaluation of fan-assisted perforations in a raised-floor data center ☆ , 2016 .

[47]  Gregory J. Michna,et al.  Flow Boiling of R134a in Circular Microtubes—Part I: Study of Heat Transfer Characteristics , 2011 .

[48]  Rahmatollah Khodabandeh,et al.  Boiling heat transfer of ammonia in vertical smooth mini channels: Experimental results and predictions , 2012 .

[49]  H. Louahlia-Gualous,et al.  An experimental study of evaporation and condensation heat transfer coefficients for looped thermosyphon , 2017 .

[50]  Liu Yang,et al.  A review on airflow distribution and management in data center , 2018, Energy and Buildings.

[51]  Yoshiyuki Abe,et al.  New Thermal Management Systems for Data Centers , 2012 .

[52]  Mohammad Ali Akhavan-Behabadi,et al.  Experimental Investigation on Flow Boiling Heat Transfer and Pressure Drop of HFC-134a inside a Vertical Helically Coiled Tube , 2012 .

[53]  Abdullah Yildiz,et al.  Thermoeconomic analysis of thermosyphon heat pipes , 2016 .

[54]  Jeffrey Rambo,et al.  Modeling of data center airflow and heat transfer: State of the art and future trends , 2007, Distributed and Parallel Databases.

[55]  Saman K. Halgamuge,et al.  A Review on efficient thermal management of air- and liquid-cooled data centers: From chip to the cooling system , 2017 .

[56]  F. Chiriac,et al.  Novel energy recovery systems for the efficient cooling of data centers using absorption chillers and renewable energy resources , 2012, 13th InterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems.

[57]  Mostafa A. Abd El-Baky,et al.  Heat pipe heat exchanger for heat recovery in air conditioning , 2007 .

[58]  Baolong Wang,et al.  Development of an integrated air conditioner with thermosyphon and the application in mobile phone base station , 2013 .

[59]  Atul Bhargav,et al.  Advances in data center thermal management , 2015 .

[60]  Yi Jiang,et al.  Three typical operating states of an R744 two-phase thermosyphon loop , 2017 .

[61]  Shuangquan Shao,et al.  A review on thermosyphon and its integrated system with vapor compression for free cooling of data centers , 2018 .

[62]  Xianting Li,et al.  Modeling and performance analysis of a two-phase thermosyphon loop with partially/fully liquid-filled downcomer , 2015 .

[63]  T. Jin,et al.  Experimental and numerical investigation on a CO2 loop thermosyphon for free cooling of data centers , 2017 .

[64]  Xiaohua Liu,et al.  An experimental investigation of an R744 two-phase thermosyphon loop used to cool a data center , 2015 .

[65]  Zhen Li,et al.  Experiment research on influence factors of the separated heat pipe system, especially the filling ratio and Freon types , 2017 .

[66]  Hoon Kang,et al.  Performance optimization of a hybrid cooler combining vapor compression and natural circulation cycles , 2009 .

[67]  Baolong Wang,et al.  Energy consumption model of integrated air conditioner with thermosyphon in mobile phone base station. , 2014 .

[68]  Guoyuan Ma,et al.  Energy-saving analysis of telecommunication base station with thermosyphon heat exchanger , 2013 .

[69]  H. Louahlia-Gualous,et al.  Experimental study and analytical modeling of thermosyphon loop for cooling data center racks , 2020, Heat and Mass Transfer.

[70]  Xiaodong Qian,et al.  Application of Heat Pipe System in Data Center Cooling , 2014 .

[71]  Predrag Stojan Hrnjak,et al.  CO2 and R410A flow boiling heat transfer, pressure drop, and flow pattern at low temperatures in a horizontal smooth tube , 2007 .

[72]  Zhen Li,et al.  Boiling heat transfer characteristics of the R744 coolant in the evaporator of the separated heat pipe system , 2017 .

[73]  A. Abdel-azim Fundamentals of Heat and Mass Transfer , 2011 .

[74]  Zhen Li,et al.  Visualization experiment on boiling heat transfer and flow characteristics in separated heat pipe system , 2018 .

[75]  Kai-Shing Yang,et al.  Investigation of Separated Two-Phase Thermosiphon Loop for Relieving the Air-Conditioning Loading in Datacenter , 2018, Energies.

[76]  Rang Tu,et al.  Retrofit of Air-Conditioning System in Data Center Using Separate Heat Pipe System , 2014 .

[77]  Aranya Chauhan,et al.  Characterization of a dual taper thermosiphon loop for CPU cooling in data centers , 2019, Applied Thermal Engineering.

[79]  Zhen Li,et al.  Analysis on energy efficiency of an integrated heat pipe system in data centers , 2015 .

[80]  Xiaodong Qian,et al.  Entransy and exergy analyses of airflow organization in data centers , 2015 .

[81]  C. Yi,et al.  Modeling and simulation of large-scale separated heat pipe with low heat flux for spent fuel pool cooling , 2019, Applied Thermal Engineering.

[82]  Kwang-Il Choi,et al.  Two-phase flow heat transfer of CO2 vaporization in smooth horizontal minichannels , 2007 .

[83]  Min Chen,et al.  Flow Boiling Heat Transfer Characteristics of R134a in a Horizontal Mini Tube , 2009 .

[86]  Chi-Chuan Wang,et al.  A review on airflow management in data centers , 2019, Applied Energy.

[87]  Thang Nguyen,et al.  Heat pipe based cold energy storage systems for datacenter energy conservation , 2011 .

[88]  Zhen Li,et al.  Modelling and applications of annual energy-using simulation module of separated heat pipe heat exchanger , 2013 .

[89]  Yi Jiang,et al.  Performance comparison of liquid desiccant air handling processes from the perspective of match properties , 2013 .

[90]  Zhang Hainan,et al.  Numerical investigation on integrated system of mechanical refrigeration and thermosyphon for free cooling of data centers , 2015 .

[91]  Zhang Hainan,et al.  Free cooling of data centers: A review , 2014 .

[92]  Eric Peterson,et al.  Hybrid cooled data center using above ambient liquid cooling , 2010, 2010 12th IEEE Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems.

[93]  Wenju Hu,et al.  Experimental investigation and economic analysis of gravity heat pipe exchanger applied in communication base station , 2017 .

[94]  Guoyuan Ma,et al.  Cooling performance of a pump-driven two phase cooling system for free cooling in data centers , 2016 .

[95]  Chang-Hyo Son,et al.  Flow boiling heat transfer and pressure drop characteristics of CO2 in horizontal tube of 4.57-mm inner diameter , 2011 .

[96]  B. Geurts,et al.  Phase change heat transfer characteristics of an additively manufactured wick for heat pipe applications , 2020, Applied Thermal Engineering.

[97]  Chayan Nadjahi,et al.  A review of thermal management and innovative cooling strategies for data center , 2018, Sustain. Comput. Informatics Syst..

[98]  Zhen Li,et al.  Current Status and Future Trends in Data-Center Cooling Technologies , 2015 .

[99]  Zhiwen Luo,et al.  Optimization of the thermal environment of a small-scale data center in China , 2020, Energy.